10.0 Using the ME-RTR Router

Why should I use Gen Run Temp? Typically, in a mobile application such

as in an RV or on a boat where the air conditioning (A/C) unit is too much

power for the inverter to run from the batteries, this feature is used to start

a generator to run the A/C unit. Many RV and marine customers travel with

pets and they do not want to leave the pets inside on a hot day. With this

feature, you could set the A/C unit to turn on and leave. Whenever the inside

temperature rises to the start setting, the generator autostarts to provide

power to the A/C unit. This would keep the area cool and comfortable – plus,

while the generator is on, the inverter batteries are being charged.
Where should I set Gen Run Temp Start? If you are using this feature to

power an A/C unit, the Gen Run Temp Start setting should be slightly above

the temperature setting of the thermostat controlling the air conditioner

unit. Once the Gen Run Temp Start setting is reached, the generator will

start providing power to the A/C unit. The reason the Gen Run Temp Start is

set above the A/C unit’s thermostat setting is to ensure the A/C unit will run

when the generator starts. If the Gen Run Temp Start setting is below that

of the A/C unit’s thermostat setting, the generator will run but the A/C unit

is not calling for a run period or cooling. In other words, your generator is

running but the power is not being used by the A/C unit – resulting in wasted

fuel and run time.

Info: If using the temperature autostart feature to start a generator

that is powering two air conditioners, it is suggested that the second

air conditioner’s thermostat be set 2° to 5° higher than the fi rst air

conditioner. This staggered setting allows the fi rst air conditioner to

start and run in an effort to keep the coach cool. If the temperature

continues to rise inside the coach, the second air conditioner turns on.

How long should I set the Gen Run Temp Time? When using the tem-

perature autostart feature, the generator autostarts and runs until the Gen

Run Temp Time setting or the SETUP: 04F Max Gen Run Time setting is

reached, whichever occurs fi rst. This means you could set the time to the

lowest time setting (0.5 Hrs), knowing the generator will attempt to run until

the temperature setting is met.

• Set Gen Run Temp Time – This menu sets the amount of time the

generator runs after a temperature autostart.
Default setting: Set Gen Run Temp Time = 2.0 Hrs
Range: 0.5 - 6.0 Hrs (0.5 hr increments)

When the temperature around the remote temperature sensor (based on

the METER: 03D AGS Temp display) increases to the Gen Run Temp Start

setting, the generator immediately starts and runs based on the Gen Run

Temp Time setting. When this run time period is fi nished, the temperature

sensor reading is checked. If the temperature sensor (or thermostat con-

trol – if using the optional pigtail adapter) reading is below the Gen Run

Temp Start setting, the generator will autostop. If the temperature sensor

(or thermostat control) reading is above the Gen Run Temp Start setting,

the generator will continue to run for a second run time period. At the end of

this second run time period, the temperature sensor reading (or thermostat

control) is checked again. This cycle continues as long as the CTRL: 03 Gen

Control menu is set to AUTO, or the SETUP: 04F Max Gen Run Time setting

is reached, whichever occurs fi rst.