11.0 ME-AGS-N Remote Status Messages

11.3 AGS Remote Fault Statuses

The following “Fault” statuses indicate that the generator wasn’t able to start

based on an expected autostart condition. Refer to Section 12.3 “ME-AGS-N

Faults using your Remote” for help in diagnosing the problem.

Table 11-3, AGS Remote Fault Statuses

STATUS

REMOTE

DESCRIPTION

Gen Run

Fault

ARC/RTR

The generator successfully started and ran

for more than two minutes, but unexpectedly

stopped before the AGS could automatically stop

the generator.

Fault

Amp

ARC/RTR

The generator failed to start in Start Amps mode.

Fault

Exercise

ARC/RTR

The generator failed to start in Start Exercise

mode.

Fault

MaxRn

ARC/RTR

The generator turned off because the SETUP: 04F

Max Gen Run Time setting had been met. This

fault can occur when: 1) an autostop parameter

has been met, but it did not stop the generator,

or, 2) the autostop condition exceeded the Max

Gen Run Time setting.

Fault SOC ARC/RTR

The generator failed to start in Start SOC mode.

Fault

Temp

RC/ARC/

RTR

The generator failed to start in Start Temp mode.

Fault Test RC/ARC/

RTR

The generator failed to start in Test mode.

Fault

Time

ARC/RTR

The generator failed to start in Start Time mode.

Fault

Topoff

ARC/RTR

The generator failed to start in Start Topoff mode.

Fault VDC RC/ARC/

RTR

The generator failed to start in Start VDC mode.