How long should I set the generator run time? This depends on whether

you are using the high temperature or low battery voltage autostart feature.

Using high temperature to autostart: When using the high tempera-

ture autostart feature, the generator autostarts and runs until the AGS:

04 Start Temp F setting is reached. This means you could set the time

to the lowest time setting (0.5 Hrs), knowing the generator will run until

the temperature setting is satisfi ed.

• Using low battery voltage to autostart: When using the low bat-

tery voltage autostart feature, the generator run time is normally set to

help re-charge the batteries. Use the table below to help determine the

generator run time setting based on the 20-hour AH capacity of your

inverter’s battery bank.

Table 8-3, Battery AmpHrs Capacity to Suggested Gen Run Time

200 to 300

1 hour

310 to 500
510 to 700
710 to 900

910 to 1100

1110 to 1300

1.5 hours

2 hours

2.5 hours

3 hours

3.5 hours

4 hours

1310 to 1500

1510 to 1700
1710 to 1900

1910 to 2100
2110 to 2300

2310 to 2500

4.5 hours

5 hours

5.5 hours

6 hours

6.5 hours

Battery

AmpHrs

Capacity

Suggested

Gen Run Time

Battery

AmpHrs

Capacity

Suggested

Gen Run Time

AGS: 04 Start Temp F Menu
This menu allows you to set and enable a temperature value that will cause

the generator to automatically start — to power an air conditioner (A/C) unit

for cooling — based on an increase in temperature, or by using an air condi-

tioning thermostat control.

Info: The optional ME-PT1 or ME-PT2 pigtail adapters can be used

to connect an air conditioner control circuit or a relay control circuit.

For more information, refer to the instruction sheet for each pigtail

adapter; either part number 64-0025 (ME-PT1 Instruction Sheet),

or 64-0026 (ME-PT2 Instruction Sheet).

This temperature autostart feature requires that the AGS’s remote tempera-

ture sensor cable (as shown in Figure 1-2) or an optional ME-PT1 or ME-PT2

pigtail adapter be connected to the REMOTE port on the AGS (see Figure

2-3). The location of the remote temperature sensor determines the area

being monitored for temperature. When the temperature around the remote

temperature sensor (based on the AGS: 08 AGS TECH menu’s Temp display)

increases to the AGS: 04 Start Temp F setting, the generator automatically

starts and runs based on the AGS: 03 Run Time Hour setting. When this run

time period is fi nished, the temperature sensor reading is checked. If the

AGS: 03 Run Time Hour Menu
This menu provides the settings that determine the length of time the gen-

erator will run once it has been autostarted by the AGS.

Default setting: Run Time = 2.0 Hrs
Range: 0.5 Hrs - 25.5 Hrs (0.5 hr increments)