8.0 Using the ME-RC Remote

© 2012 Magnum Energy, Inc.

28

8.0 Using the ME-RC Remote

The ME-RC remote’s AGS menus under the AGS and TECH buttons allow

you to customize and monitor the operating parameters for your autostart/

autostop generator system. To help confi gure and operate the AGS with your

ME-RC, refer to the mini index below to direct you to the appropriate section.

8.1 ME-AGS-N Setup using the ME-RC

page 28

8.2 ME-AGS-N Functional Testing using the ME-RC

page 33

8.3 ME-AGS-N Operation/Monitoring using the ME-RC

page 34

8.4 Enabling the ME-AGS-N using the ME-RC

page 36

8.5 Starting and Stopping the Generator using the ME-RC

page 36

8.6 ME-AGS-N Menu Map using ME-RC

page 37

Figure 8-1, ME-RC’s AGS Confi guration Access Buttons

Inverting

DC 12.6V 5A

Status...

01 AGS Control

SHORE

AGS METER SETUP TECH

AGS and TECH Buttons

8.1 ME-AGS-N Setup using the ME-RC

Press the AGS button on ME-RC remote (Figure 8-1), and then rotate the

SELECT knob to navigate to the AGS menus. These menus allow the genera-

tor to be automatically started and stopped based on different parameters.

Using Table 8-1, determine the specifi c autostart and autostop condition with

which you want the generator to be automatically controlled, and then use

that specifi c menu setting to confi gure the AGS.
Note: For information on using the AGS: 01 AGS Control, AGS: 02 AGS Sta-

tus, and AGS: 08 AGS TECH menus, refer to Section 8.3 “ME-AGS-N Opera-

tion/Monitoring using the ME-RC”.

This AGS manual covers ME-RC remote controls with a revision of 1.5 to

2.612. There may be differences between revisions that affect your AGS

setup/operation. Use Table 8-2 to familiarize yourself with the differences

between AGS revisions.

Info: Refer to your ME-RC owner’s manual to determine your remote’s

revision (or see the AGS: 08 AGS TECH menu section on page 35).

Table 8-1, ME-RC Autostart/Autostop Matrix

Autostart

Condition

See AGS

Menu

Page

Autostop

Condition

See AGS

Menu

Page

Gen starts on high

temperature

04 Start

Temp F

30

Gen stops

after a set

time period

03 Run

Time Hour

30

Gen starts on low

inverter battery

voltage

05 Start

Volts

32