11.0 ME-AGS-N Remote Status Messages

© 2012 Magnum Energy, Inc.

86

Table 11-2, AGS Remote Start Statuses

STATUS

REMOTE

DESCRIPTION

Start Amp ARC/RTR

The generator has started based on the SETUP:

04C Gen Run Amps setting.

Start
Exercise

ARC/RTR

The generator has started based on the SETUP:

04H Gen Exercise setting.

Start SOC

ARC/RTR

The generator has started based on the SETUP:

04D Gen Run SOC setting.

Start

Temp

RC

The generator has started based on the AGS: 04

Start Temp setting.

ARC/RTR

The generator has started based on the SETUP:

04E Gen Run Temp setting.

Start Test

RC/ARC/

RTR

The AGS is in Test mode. Test mode may be

started from the TEST button located on the

AGS,

RC

or, by selecting “Test” from the AGS: 01 AGS

Control menu (see Section 5.1 for further infor-

mation on the AGS’s TEST button).

Start Time ARC/RTR

The generator has started based on the SETUP:

04B Gen Run Time setting.

Start

Topoff

ARC/RTR

The generator has started based on the SETUP:

04G Quiet Time Topoff Time setting.

Start VDC

RC

The generator has started based on AGS: 05

Start Volts setting.

ARC/RTR

The generator has started based on SETUP: 04A

Gen Run VDC setting.

11.2 AGS Remote Start Statuses

The following “Start” statuses identify the condition that autostarted the

generator. If you determine that the autostart condition occurred sooner

than expected (or didn’t want this autostart condition), refer to the Setup

section for your specifi c remote to change (or defeat) the autostart setting.