background image

8.0 Using the ME-RC Remote

© 2012 Magnum Energy, Inc.

34

8.3 ME-AGS-N Operation/Monitoring using the ME-RC

This section covers the AGS menus in the ME-RC remote that determine how

to control and operate the generator. The section also includes menus that are

used to monitor starting and running conditions for the AGS and the generator.

• Enable – Select this option to have the AGS monitor temperature (04

Start Temp F) and/or the inverter’s battery voltage (05 Start Volts) to

determine when to automatically start the generator.

• Test

– Select this option to test the generator. This option starts the

generator, runs it for approximately 30-60 seconds, and then stops the

generator. Use this setting for testing generator wiring and operation.

After a successful start/stop sequence test, this selection returns to Off.

• Enable

w/QT – Select this option to have the AGS monitor tempera-

ture (04 Start Temp F) and/or the inverter’s battery voltage (05 Start

Volts) to determine when to automatically start the generator – with the

Quiet Time parameters enabled.

WARNING:

Never allow the generator to start/run in an enclosed

garage or any other type of enclosed structure without proper ven-

tilation. Carbon monoxide, an odorless, colorless, deadly gas may

accumulate and cause serious injury or death.

AGS: 02 AGS Status Menu
This menu allows you to view the AGS’s current status. There are 13 dif-

ferent status messages to identify the AGS’s current state, but only one is

displayed at any one time (refer to the AGS menu map – Figure 8-2).
Available statuses are (refer to Tables 11-1 thru 11-3 for detailed descrip-

tions of each):

• AC

In

• Manual

Run

• No

Comm

• Fault

Temp

• Fault

Test

• Fault

VDC

• Lockout

8.3.2 Monitoring the AGS using the ME-RC

The following menus are helpful for the proper operation and monitoring

of your AGS/generator system. Press the AGS button, and then rotate and

press the SELECT knob to access the following menus:

8.3.1 Controlling the AGS using the ME-RC

Press the AGS button, and then rotate and press the SELECT knob to access

the following menus:
AGS: 01 AGS Control Menu
This menu is used to enable the AGS (selecting Enable or Enable

w/QT). A “Test” setting is also available to ensure the start/stop wiring from

the generator to the ME-AGS-N is correct. The available settings are:
• Off – This option disables the AGS’s generator start/stop functions. It

also turns the generator off if it is running from an autostart command.

When Off is selected, the generator will not start automatically. This is

the default setting. If you have an AGS fault, select Off to clear the fault.

Info: If DC power is lost to the remote or to the system, this menu

resets to the default Off position for safety.

• Off
• Quiet

Time

• Ready

• Start

Temp

• Start

Test

• Start

VDC