8.0 Using the ME-RC Remote

AGS Menu

(Button: Menu)

AGS Menu

Selections/Adjustments

Inverter

Level

ME-AGS-N

Required

ME-RC

Required

AGS: 01 AGS

Control

Off, Enable, Test, Enable

w/QT

≥ Level 1 ≥ Rev 5.0

≥ Rev 1.5

AGS: 02 AGS

Status

Read Only

≥ Level 1 ≥ Rev 5.0

≥ Rev 1.5

AGS: 03 Run

Time Hour

0.5 - 6.0 Hours

≥ Level 1 ≥ Rev 5.0

≥ Rev 1.5

0.5 - 25.5 Hours

≥ Level 1 ≥ Rev 5.0

≥ Rev 2.6

AGS: 04 Start

Temp F

Off, 65 - 90F

≥ Level 1 ≥ Rev 5.0

≥ Rev 1.5

Off, Ext Input, 65 - 90F

≥ Level 1 ≥ Rev 5.0

≥ Rev 2.1

Off, Ext Input, 65 - 95F

≥ Level 1 ≥ Rev 5.0

≥ Rev 2.5

AGS: 05 Start

Volts

Off, 10.0-12.2, 20.0-24.4,

VDC

≥ Level 1 ≥ Rev 5.0

≥ Rev 1.5

Off, 10.0-12.2, 20.0-24.4,

40.0-44.8 VDC

≥ Level 1 ≥ Rev 5.0

≥ Rev 1.6

AGS: 06 Set

Time

12:00A-12:00P

≥ Level 1 ≥ Rev 5.0

≥ Rev 1.5

AGS: 07 Quiet

Time

Off, 9PM-7AM, 9PM-8AM,

9PM-9AM, 10PM-8AM,

11PM-8AM

≥ Level 1 ≥ Rev 5.0

≥ Rev 1.5

AGS: 08 AGS TECH

Gen Run

Read Only

≥ Level 1 ≥ Rev 5.0

≥ Rev 1.5

*

AGS VDC

Read Only

≥ Level 1 ≥ Rev 5.0

≥ Rev 1.5

AGS Rev

Read Only

≥ Level 1 ≥ Rev 5.0

≥ Rev 1.5

Temp

Read Only

≥ Level 1 ≥ Rev 5.0

≥ Rev 1.5

AGS Mode

RV, Other

≥ Level 1 ≥ Rev 5.0

≥ Rev 2.5

TECH: 01

Temperatures

AGS: Read Only

≥ Level 1 ≥ Rev 5.0

≥ Rev 1.5

TECH: 02

Revisions

AGS: Read Only

≥ Level 1 ≥ Rev 5.0

≥ Rev 1.5

Active AGS Fault

Fault LED = off, Fault

status = view under AGS:

02 AGS Status

≥ Level 1 ≥ Rev 5.0

≥ Rev 1.5

Fault LED = blinking, Fault

status = alternates with

inverter/charger status

≥ Level 1 ≥ Rev 5.0

≥ Rev

2.612

*

Requires ME-AGS-N Rev. 5.2 or higher

Table 8-2, Software Differences Between ME-RC Revisions