0 installation, On generator, Inside generator – Magnum Energy AGS Network (ME-AGS-N) User Manual
Page 18

2.0
Installation
© 2012 Magnum Energy, Inc.
12
Figure 2-10, Generator Run Sense Options
negative
DC Fuse
(5A max)
run sense
AGS Terminal Block Ports:
1
2
3
4
5
6
7
8
On Generator
120VAC Outlet
120VAC IN
12VDC OUT
TRANSFORMER
120 VAC Coil Relay
On Generator
NC
COM
NEU
HOT
NO
120VAC Outlet
Inside Generator
Generator
Battery
negative
run sense
AGS Terminal Block Ports:
1
2
3
4
5
6
7
8
DC Fuse
(5A max)
Generator
Battery
Inside Generator
Generator
Running
Lamp
OR
Generator
Hour
Meter
0
1
2
3
negative
DC Fuse
(5A max)
run sense
AGS Terminal Block Ports:
1
2
3
4
5
6
7
8
Alternative Option 3 – Use an external 120 VAC coiled relay to bring the
generator’s battery voltage to the AGS gen run sense terminal (AGS terminal
block – Terminal #2) only while the generator is running. The generator’s
battery voltage must be 10 to 40 VDC.
Alternative Option 2 – Use a 120 VAC to 12 VDC step-down transformer
(normally used to charge power equipment batteries) and plug it into the
generator’s 120 VAC output. The step-down transformer provides 12 VDC
output only while the generator is running.
Alternative Option 1 – Tap into the positive side of the generator’s hour
meter or running lamp; ensure the voltage is 10 to 40 VDC only while the
generator is running.