0 installation, On generator, Inside generator – Magnum Energy AGS Network (ME-AGS-N) User Manual

Page 18

background image

2.0

Installation

© 2012 Magnum Energy, Inc.

12

Figure 2-10, Generator Run Sense Options

negative

DC Fuse

(5A max)

run sense

AGS Terminal Block Ports:

1

2

3

4

5

6

7

8

On Generator

120VAC Outlet

120VAC IN

12VDC OUT

TRANSFORMER

120 VAC Coil Relay

On Generator

NC

COM

NEU

HOT

NO

120VAC Outlet

Inside Generator

Generator

Battery

negative

run sense

AGS Terminal Block Ports:

1

2

3

4

5

6

7

8

DC Fuse

(5A max)

Generator

Battery

Inside Generator

Generator

Running

Lamp

OR

Generator

Hour

Meter

0

1

2

3

negative

DC Fuse

(5A max)

run sense

AGS Terminal Block Ports:

1

2

3

4

5

6

7

8

Alternative Option 3 – Use an external 120 VAC coiled relay to bring the

generator’s battery voltage to the AGS gen run sense terminal (AGS terminal

block – Terminal #2) only while the generator is running. The generator’s

battery voltage must be 10 to 40 VDC.

Alternative Option 2 – Use a 120 VAC to 12 VDC step-down transformer

(normally used to charge power equipment batteries) and plug it into the

generator’s 120 VAC output. The step-down transformer provides 12 VDC

output only while the generator is running.

Alternative Option 1 – Tap into the positive side of the generator’s hour

meter or running lamp; ensure the voltage is 10 to 40 VDC only while the

generator is running.