10.0 Using the ME-RTR Router

10.4 Enabling the ME-AGS-N using the ME-RTR

Before the AGS can begin operating and monitoring for an autostart condition

(using the active AGS settings in your ME-RTR router), it must be enabled.
From the AGS Home screen (to access, refer to info in Section 10.2.1.1):
1. Press the CTRL button on the ME-RTR router, and then rotate the SELECT

knob to the 03 Gen Control menu.

2. Press the SELECT knob. The Set Gen Control screen displays with the

current gen control setting and an arrow to the right.

10.5 Starting and Stopping the Generator using the

ME-RTR

Using the available settings from your ME-RTR router, the generator can be

manually and automatically started/stopped.
To autostart/autostop the generator:
In order for the generator to autostart/autostop, one or more of the follow-

ing autostart/autostop conditions must be pre-set (see Section 10.1):

The AGS is now ready to automatically start/stop the generator once an

autostart condition is satisfi ed.
Note: If power is lost to your remote, the AGS control setting will return to the

default OFF setting. Once power is restored, you must enable the AGS again.
Note: Despite enabling the AGS, you must check the AGS’s current status

(either by viewing the AGS Home screen or under the METER: 03A AGS Status

menu) and ensure the status displays as “Ready”.

3. Turn the SELECT knob to the AUTO setting.
4. Press the SELECT knob to select this setting. The selection arrow appears

to the right of the screen

TECH: 03 Firmware Versions
This menu displays the software/fi rmware version of all the network devices

connected directly to the network ports of the connected inverter. (P1acc-

P6acc). If an AGS is connected, the screen alternates the “AGS” display with

the revision of the connected AGS.

Info: The AGS accessory may display a “0.0” revision for several

reasons. Either the AGS is not installed, there is no communica-

tion because of a bad or miswired network cable, or the AGS is not

powered or is bad.

Autostart Conditions

04A Gen Run VDC (pp. 62-64)

04B Gen Run Time (p. 65)

04C Gen Run Amps (pp. 65-66)

04D Gen Run SOC (pp. 66-67)

04E Gen Run Temp (pp. 67-68)

04G Quiet Time (pp. 69-71)

04H Gen Run Exercise (pp. 71-72)

Autostop Conditions

04A Gen Run VDC (pp. 62-64)

04B Gen Run Time (p. 65)

04C Gen Run Amps (pp. 65-66)

04D Gen Run SOC (pp. 66-67)

04E Gen Run Temp (pp. 67-68)

04F Max Gen Run Time (p. 69)

04G Quiet Time (pp. 69-71)

04H Gen Run Exercise (pp. 71-72)