5.0 ME-AGS-N Module Operation

© 2012 Magnum Energy, Inc.

22

5.0 ME-AGS-N Module Operation

This section details the operation of the ME-AGS-N module (independent of

the remote control operation).

5.1 ME-AGS-N Module TEST Pushbutton

The front of the module (Figure 5-1) has a red pushbutton to test the AGS

system operation. When the red TEST pushbutton is pressed and released,

the AGS initiates an automatic generator start/stop sequence. This test

attempts to turn the connected generator on and to have it run for at least

30 seconds before turning off. This start/stop test is used to confi rm that

all wiring from the generator to the AGS is correct and that the AGS is

confi gured correctly for your generator type.
Note: If the generator is running from an autostart condition when the AGS

module’s TEST button is pressed, the AGS will turn the generator off and

initiate an automatic generator start/stop test sequence (running 30-60

seconds) – using 4 autostart attempts if needed.

5.2 ME-AGS-N Module LED Indicators

The front of the module (Figure 5-1) has two LED indicators for viewing

system operation.

5.2.1 STATUS LED Indicator

Blinking Green: Indicates that the AGS system is initiating a generator

start sequence. This happens when the TEST button (on the AGS) has been

pressed and released, or a remote control has communicated to the AGS to

autostart the generator.
Solid Green: Indicates the generator has started successfully and is providing

the gen run sense signal/voltage to the AGS module.
Solid Red: Indicates a fault condition in which the generator either has not

started, or has not provided the correct run gen sense signal/voltage to the

AGS module – after four start attempts.

5.2.2 READY LED Indicator

Solid Green: Indicates the AGS module has power and the temperature sen-

sor cable is detected. This indicates normal AGS system operation.
Blinking Green: Indicates that the AGS module has power, but the tempera-

ture sensor is not detected. This can mean the temperature sensor cable is

either not connected, incorrectly connected, or is defective.
Note: The temperature sensor is not required to be connected unless the

temperature autostart feature is needed.

Figure 5-1, ME-AGS-N Front Panel Controls and Indicators

READY

Indicator

(green)

STATUS

Indicator

(green/red)

TEST