beautypg.com

Setup: 04f max gen run time menu, Setup: 04g quiet time menu, 0 using the me-rtr router – Magnum Energy AGS Network (ME-AGS-N) User Manual

Page 75

background image

69

© 2012 Magnum Energy, Inc.

10.0 Using the ME-RTR Router

SETUP: 04G Quiet Time Menu
This menu is used to enable the Quiet Time feature, and to set the period

of time each day in which the generator is not allowed to automatically run.

The Quiet Time start setting will prevent the generator from starting even

if one of the start parameters is met. If any autostart parameter in the 04

AGS Setup menus has been met and the generator is running when the Quiet

Time start setting is reached, the generator will turn off. The generator will

not try to autostart until the Quiet Time stop setting has been reached and

an autostart condition is once again satisfied.

The ME-ARC contains a real time clock that must be set for proper

operation of the SETUP: 04G Quiet Time Menu feature.

Set Quiet Time Set to ON (allows you to set the start and stop times).
Default setting: Set Quiet Time = OFF
Range: OFF, ON, [daily start and stop time settings (12:00AM-12:00PM)]

Info: When the generator autostarts from one of the autostart set-

tings, it will autostop when the autostop parameter for that particu-

lar setting has been satisfi ed. For example, if the generator starts

due to the 04A Gen Run VDC menu’s autostart setting, it then stops

once it satisfi es the Stop Gen Volts autostop setting. However, the

Max Gen Run Time setting overrides any autostop setting. If the

generator stops because the Max Gen Run Time setting has been

reached, the Fault MaxRun status will occur. If this happens, you

may have to increase the Max Gen Run Time setting or adjust the

autostop setting to fi nish sooner. If multiple autostart settings are

set in the 04 AGS Setup menus and a Fault MaxRun status occurs,

refer to the METER button’s 03A AGS Status menu to identify which

condition autostarted the generator. This way you will know which

auto condition is running longer than the Max Gen Run Time setting.

Info: The Max Gen Run Time menu uses the METER button’s 03C

Gen Run Time display to determine the generator’s run time.

Info: If the generator is stopped due to the Max Gen Run Time param-

eter being met, the status becomes Fault MaxRn and the generator

will not autostart again until you clear the fault.

SETUP: 04F Max Gen Run Time Menu
This menu is used to set the maximum time the generator will run if the

generator has been started by one of the AGS’s autostart settings.
• Set Max Gen Run Time – Set the maximum amount of time you want

the generator to run once it has been autostarted.
Default setting: Set Max Gen Run Time = 12.0 Hrs
Range: 0.0 - 25.0 Hrs (0.1 hr increments)

Why should I use Max Gen Run Time? This setting is used to ensure the

generator does not run longer than desired after an autostart. Designating

a maximum run time ensures that the generator will stop if the autostop

setting cannot be satisfi ed. For example, if you know the fuel capacity of

your generator is 5 hours, set the Max Gen Run Time setting to 4.5 hours to

ensure the generator does not run out of fuel.