0 me-ags-n remote status messages – Magnum Energy AGS Network (ME-AGS-N) User Manual
Page 91

85
© 2012 Magnum Energy, Inc.
11.0 ME-AGS-N Remote Status Messages
Table 11-1, AGS Remote Operational Statuses (cont.)
STATUS
REMOTE
DESCRIPTION
Gen
Warm-up
ARC/RTR
The AGS is attempting to start the generator and
a time period has been set under the SETUP: 04I
Gen Warm-up Time setting. Once the AGS sta-
tus indicates “Warm-up”, the inverter/charger’s
AC input ignores any incoming AC power. This
prevents the inverter/charger from loading the
generator during warm-up. Once the AGS has
determined that the generator is running, the
warm-up time setting must be met before the
generator can connect to the inverter/charger.
Manual
Run
RC
The generator was started manually from a start/
stop switch directly connected to the generator,
and the AGS Mode is set to Other (if the AGS
Mode=RV, a Lockout fault displays instead).
ARC/RTR
The generator was started manually from a start/
stop switch directly connected to the generator,
or from the CTRL: 03 Gen Control menu.
Note: The AGS determines that the generator has been manually turned
on by sensing a gen run sense voltage to Terminal #2 on the AGS’s 8-port
terminal block. However, if the Gen Type DIP switch is set to “2-Wire
Standby” — which does not require a gen run sense voltage — manually
turning the generator on displays a status of AC In rather than Manual
Run.
Quiet
Time
RC
The ME-AGS-N has entered Quiet Time per the
AGS: 07 Quiet Time setting.
ARC/RTR
The AGS has entered Quiet Time per the SETUP:
04G Quiet Time setting.
Note: The generator will not autostart during Quiet Time.
Lockout
RC
Lockout occurs when the AGS system is automat-
ically disabled because the generator has been
started or stopped for any condition outside the
control of the AGS. This an RVIA requirement,
refer to the information on the AGS mode under
the AGS: 08 AGS TECH menu on page 35.
Note: When a Lockout status occurs, the AGS: 01 AGS Control menu au-
tomatically changes from Enable (or Enable w/QT) to Off.
For assistance in clearing or disabling this status, refer to Section 12.2
“Resolving Operational Statuses”.
Note: In installations where the requirement to automatically disable the
AGS system is not needed, the AGS mode can be changed to “Other”.
Refer to the information on the AGS mode under the AGS: 08 AGS TECH
menu on page 35.