11.0 ME-AGS-N Remote Status Messages

© 2012 Magnum Energy, Inc.

84

11.0 ME-AGS-N Remote Status Messages

A status message may be an operational or fault message. Access the AGS

status menu (METER button’s 03A AGS Status menu for ME-ARC and ME-

RTR; AGS button’s 02 AGS Status menu for ME-RC) to view the AGS’s cur-

rent operating status. This menu is important when determining if the AGS

is working correctly, or for troubleshooting an AGS installation.

11.1 AGS Remote Operational Statuses

Refer to Table 11-1 for a brief description of the possible AGS operational

statuses that may display (depending on your remote).
Note: RC = ME-RC, ARC = ME-ARC, and RTR = ME-RTR

STATUS

REMOTE

DESCRIPTION

Ready

RC

The AGS: 01 AGS Control menu is set to Enable

or to Enable w/QT, and the AGS is ready to au-

tomatically start the generator based on the AGS

button’s active autostart settings.

ARC/RTR

The CTRL: 03 Gen Control menu is set to AUTO,

and the AGS is ready to automatically start the

generator based on the active autostart settings

under the SETUP: 04 AGS Setup menu.

No Comm

RC/ARC/

RTR

The AGS is not communicating with the inverter/

remote.
This is a normal status if there is no AGS (Net-

work version) connected in the system.
If an AGS is installed, then refer to Section 12.2

“Resolving Operational Statuses” for assistance.

AC In

RC/ARC/

RTR

The inverter/charger is connected to another

source such as a grid or an alternate generator,

and is not controlled by the AGS. When AC In

displays, the AGS is prevented or locked out from

all autostarting conditions, except for when the

generator needs to exercise – if enabled.

Off

RC

The AGS: 01 AGS Control menu is set to Off. This

setting will not allow the AGS to autostart the

generator.

ARC/RTR

The CTRL: 03 Gen Control menu is set to OFF.

This setting will not allow the AGS to autostart

the generator.

Gen

Cooldown

ARC/RTR

The autostop setting has been satisfi ed in one

of the generator autostart/autostop menus, and

the generator has been disconnected from the

inverter/charger. However, the generator is still

running until the cooldown time is met (as per

the SETUP: 04J Gen Cooldown Time setting).

Table 11-1, AGS Remote Operational Statuses