beautypg.com

0 installation – Magnum Energy AGS Network (ME-AGS-N) User Manual

Page 19

background image

13

© 2012 Magnum Energy, Inc.

2.0 Installation

2.5.3 Gen Start/Stop Connections (Terminals 1, 5, 6, 7,

&

8)

This section covers the control relays inside the AGS module, and provides

information about wiring these relays to the generator’s start/stop circuit.

You must identify the generator’s start and stop wiring requirements in

order to determine: how many relays you require, the number of wires you

connect, and in what combination.
When the generator is equipped with a remote control terminal or connector,

it is much easier to make the connections to the AGS control relays if

the generator‘s optional remote control is purchased. Connecting to the

generator’s remote also eliminates the need to make connections inside the

generator (and possibly violating the generator’s warranty).
The AGS module provides three control relays (RY1, RY2, and RY3) to

operate the autostart/autostop functions of your generator. These relays are

dry contacts (they do not provide any voltage or current), and operate only

as switches that turn low amperage devices (≤5 amps) on and off. They

are not intended to directly provide power to starter motors or to ignition

systems. Rather, the relays are used to send a signal to operate the coil of

another higher amperage device, which does the actual switching of power.

CAUTION: A fuse rated at 5 amps or less must be used to protect

each of the relays. The warranty does not cover damage to these

relays. Fuses should be located as close as possible to the generator

connection. A fuse must be used, even if the circuit is providing only

a “dry contact” or “ground” connection – it will prevent damage if

the connection is miswired or damaged.

Info: To set the generator type — which determines the operation

of the AGS relays — see the Gen Type setting info in Section 3.1.

Info: Due to the different generator types and the various starting/

stopping wiring confi gurations used by generator manufacturers,

detailed wiring instructions are not provided in this manual. Please

refer to your generator’s documentation for wiring details.
Info: For more information, and to view diagrams on connect-

ing the AGS to the start/stop circuit on many generators, go to

http://www.magnumenergy.com/service/genwiringdiagrams.htm.

Depending on your generator’s start and stop wiring requirements, you may

only need to use one relay (RY1) for fully automatic 2-wire generators; two

relays (RY1 and RY2) for 3-wire generators; or all three relays (RY1, RY2,

RY3) for generators that require an independent bypass or preheat circuit.
The connection points to each relay are as follows (see Figure 2-11):
• Relay 1 (RY1) and Relay 2 (RY2)

Terminal #5: the Normally Open (N.O.) position of the RY1 relay
Terminal #6: the Common (COM) position of both Relay 1 (RY1) and

Relay 2 (RY2)
Terminal #7: the Normally Open (N.O.) position of Relay 2 (RY2)

• Relay 3 (RY3)

Terminal #1: the Common (COM) position of Relay 3 (RY3)
Terminal #8: the Normally Open (N.O.) position of Relay 3 (RY3)