0 installation, Inside generator, Relay timing for gen type: 5-wire mode – Magnum Energy AGS Network (ME-AGS-N) User Manual

Page 23

background image

17

© 2012 Magnum Energy, Inc.

2.0 Installation

Monitored

battery bank

(12V/24V/48V)

≤5

amp

fuse

≤5

amp

fuse

≤5

amp

fuse

Inside Generator

Gen

Battery

Gen

Hour Meter

0 1 2 3

PREHEAT

START

STOP

≤5

amp

fuse

GEN AND POWER I/O

Relay 1

(Terminals 5 & 6)

Relay 2

(Terminals 6 & 7)

Relay timing for Gen Type: 5-Wire Mode

STOP

Time

START

Time

Time between start attempts

10 sec.
10 sec.

4 sec.

Timing Information

Total start attempts

2 min.

PREHEAT

Time

25 sec.

Relay 3

(Terminals 1 & 8)

Start

Delay

Delay

GEN RUN

PERIOD

PREHEAT

START

STOP

STOP

4

Preheat delay time

Start Delay Time

14 sec.

Connected via

communication cable to

inverter’s Network port

12/24/48V

Gen Type

(5-Wire

Mode)

Input DC Voltage

Jumper - set to

monitored battery

bank voltage

(on 24V setting)

INSIDE

INSIDE

ON

4
3
2
1

Figure 2-14, Three-wire Momentary Control Type Generators