beautypg.com

0 me-ags-n module functional tests, 1 power-up test, 2 generator wiring test – Magnum Energy AGS Network (ME-AGS-N) User Manual

Page 27

background image

21

© 2012 Magnum Energy, Inc.

4.0 ME-AGS-N Module Functional Tests

4.0 ME-AGS-N Module Functional Tests

After all electrical connections

to the AGS module, batteries, and generator

have been completed (and prior to reconnecting the green 8-port terminal

block), perform the following tests to verify that the AGS system is function-

ing correctly and the wiring from the AGS to the generator is correct. Once

the AGS module passes the functional tests, you can set up the AGS for

your autostart and autostop requirements (refer to: Section 8.0 for a ME-RC

controller, Section 9.0 for a ME-ARC, or Section 10.0 if you have a ME-RTR).
Note: The communication cable from the inverter to the green NETWORK

port on the AGS is not required in order to perform these tests.

4.1 Power-Up Test

1. Before connecting the 8-port terminal block into the AGS module, use a

multimeter to verify the correct polarity and that the voltage to Terminals

#3 (positive) and #4 (negative) is correct according to the position of

the input DC voltage jumper (refer to Figure 3-2).

2. Apply power to the AGS module by plugging in the green 8-port terminal

block into the module, and then verify that the green READY LED comes

on and the STATUS LED blinks green once.

Info: The green READY LED will come on (solid) when the AGS module

is powered and the temperature sensor is connected, and will blink

if the temperature sensor is not connected or detected. A connected

temperature sensor is not required unless the temperature autostart

feature is needed.

4.2 Generator Wiring Test

This start/stop test is used to confi rm that all wiring from the generator to

the AGS module is correct and the Gen Type setting (Table 3-1) is confi gured

correctly for your generator type.
1. Press and release the red TEST button on the AGS (see Figure 5-1).
2. The STATUS LED on the AGS module will begin to blink green and the

generator should start (a blinking green STATUS LED means the AGS has

initiated an automatic generator start/stop sequence).

3. Once the generator starts, it should run for approximately 30-60 seconds

before automatically turning off (ensure the it will not try to restart within

the next two minutes). View the STATUS LED and ensure it turns solid

green (a solid green STATUS LED means the generator has started suc-

cessfully and is providing the gen run sense signal to the AGS module¹).

Note: If the generator attempted to start but did not run, continue to wait,

the AGS will attempt to start the generator 3 more times.
If your AGS/generator system passes all steps above (may attempt an auto-

start 4 times), then the wiring from the AGS to the generator is correct. You

are now ready to set up and activate the AGS using your remote control panel.

Info: The AGS attempts to start the generator 4 times. If after 4

attempts the generator fails to start, the STATUS LED turns red –

indicating a fault.

If the generator did not start, or the STATUS LED shows a fault condition (solid

red LED indication), refer to Section 6.0 “ME-AGS-N Module Troubleshooting”.
Note¹: The gen run sense signal from the generator to Terminal #2 on the

AGS is not required when using the 2-Wire Standby Mode (Gen Type setting).