beautypg.com

5 me-ags-n terminal block wiring connections, 0 installation – Magnum Energy AGS Network (ME-AGS-N) User Manual

Page 16

background image

2.0

Installation

© 2012 Magnum Energy, Inc.

10

2.5 ME-AGS-N Terminal Block Wiring Connections

With the AGS already mounted, remove the green 8-port terminal block before

proceeding with wiring the generator. Refer to Figure 2-11 and the info below

to wire the AGS’s terminal block to the generator.

CAUTION: DO NOT plug in the 8-port terminal block until all the

wiring to the module is complete and you are ready to perform the

functional tests (per instructions in Section 4.0).
CAUTION: A fuse rated at 5 amps or less must be used to protect

all power circuits connected to the AGS (do not fuse ground connec-

tions). Ensure the fuse is correctly rated for the wire size used. Refer

to national and local codes for rating and type. Normally, a minimum

#16 AWG wire is required in order to use a 5-amp fuse.

Info: The green 8-port terminal block accepts CU/AL conductors from

#30 to #12 AWG (0.05 to 3.3 mm

2

).

2.5.1 Power Connections (Terminals 3

&

4)

Terminals #3 (positive) and #4 (negative) on the 8-port terminal block are

connected to the monitored battery bank*. These terminals are used to power

the AGS module and to monitor the inverter’s battery voltage (when used to

autostart the generator based on low battery voltage).

Info: The AGS requires a DC input of 8.5-70 volts in order to operate

the internal relays. An input voltage greater than 70 volts will cause

damage to the AGS and is not covered by the product warranty.

* Monitored Battery Bank – When autostarting the generator based on battery

voltage (i.e., start VDC), the inverter’s battery bank must be connected to Termi-

nals #3 (positive) and #4 (negative). If autostarting based on any other condition

(i.e., temperature, amps, etc.), either the inverter battery bank or the generator’s

battery may be used to power the AGS module. However, the negative terminal

of every battery bank must be connected together to prevent damage to the AGS

(see Section 2.4.4).

2.4.4 Ensure all Negative Connections are Connected Together

When connecting devices together (via a network communication cable),

the return path (i.e., battery negative) of each battery powered device must

be at the same potential (i.e., electrically common with each other). This

prevents a high-impedance path developing between the connected devices,

which can cause the network cable to become the DC return path to the

battery – possibly resulting in permanent damage to all connected devices

on the network. This also requires that the battery negative connection of

each device be always connected before connecting/disconnecting any bat-

tery positive.

Network cable

Inverter

Battery

Inverter

Battery

AGS

Inverter

Figure 2-9, Connected Devices at the Same Potential