Yaskawa MP3200 Troubleshooting Manual User Manual
Page 32

2.2 CPU Unit/CPU Module Indicators and Display
Display
2-10
E061:
Unit configuration
error
−
There is a configuration
error on Rack .
: 1 to 7
Check the following con-
ditions.
• There are more than
three MP3000 Units.
• There is more than one
MP2000 Unit.
• There is more than one
Sub CPU.
• There are more than two
Base Units.
• An MP2000 Unit is
mounted to Rack 5 to 7
(excluding to the right of
a Sub CPU).
• More than one EXIOIF
Module is mounted.
• An EXIOIF Module is
mounted under a Sub
CPU.
Correct the Unit con-
figuration.
E062:
Unit configuration
error
−
E063:
Unit configuration
error
−
E064:
Unit configuration
error
−
E065:
Unit configuration
error
−
E066:
Unit configuration
error
−
E067:
Unit configuration
error
−
E070:
Unsupported Sub
CPU mode
−
A CPU version that does
not support operation as a
Sub CPU was mounted as
a Sub CPU.
Check the system soft-
ware version.
Use a version of the
CPU that supports
operation as a Sub
CPU.
E071:
Unsupported Module
detected
A Module that cannot be
used was mounted.
Check to see if the Mod-
ules are supported.
Remove any Modules
that are not supported.
E080:
CPU mode mismatch
−
The Main CPU contains a
Sub CPU project.
Or a Sub CPU contains a
Main CPU project.
Log on from the MPE720
and check the Module con-
figuration definitions.
Transfer a Main CPU
project to the Main
CPU. Transfer a Sub
CPU project to the
Sub CPU.
E081:
CPU stopped for
internal temperature
error 1
The temperature contin-
ued to increase even fur-
ther after A241 was
detected and is approach-
ing the permissible tem-
perature of the internal
parts.
Check SB00041F (tem-
perature warning).
Change the installa-
tion environment to
lower the temperature
around the CPU.
If the CPU tempera-
ture increases and an
error occurs, turn OFF
the power supply to
the Controller and
change the installa-
tion environment.
E082:
CPU stopped for
internal temperature
error 2
The temperature contin-
ued to increase even after
E081 was detected and has
reached the permissible
temperature of the internal
parts.
E083:
Fan stopped (1 min-
ute)
−
The Fan stopped continu-
ously for 1 minute.
Check to see if the Fan is
operating.
Or, check SB00041E (Fan
error).
Check the Fan opera-
tion.
If the Fan is not oper-
ating, turn OFF the
power supply to the
Controller and replace
the Fan.
Continued on next page.
Continued from previous page.
Alarm Code
Alarm Name
MP3200
MP3300
Cause
Confirmation Method
Correction