Do-01 error status – Yaskawa MP3200 Troubleshooting Manual User Manual
Page 157

7.5 System Register Configuration and Error Status
Error Status for Individual Products
7-31
T
roubleshooting System Errors
Valid Ranges for AI/AO Adjustment Values
Offset: -9,999 to 9,999
Gain: 0.0001 to 1.9999
DO-01 Error Status
Table 7.15 MIXIO Error Status Details
Item
Code
Remarks
Error code
0
No error
2
I/O Error
FLT
0
Oscillator and ASIC for AO are normal.
1
Oscillator error or error in ASIC for AO
FUSE
0
Fuse normal
1
Fuse error
ADJI
0
AI shipping adjustment value normal
1
AI shipping adjustment value not set or
adjustment value error
ADJO
0
AO shipping adjustment value normal
1
AO shipping adjustment value not set or
adjustment value error
Table 7.16 CNTR-A Error Status Details
Item
Code
Remarks
Error code
0
No error
2
I/O Error
FLT
0
Counter ASIC normal
1
Counter ASIC error
PA
0
Phase A normal
1
Phase A disconnection detected
PB
0
Phase B normal
1
Phase B disconnection detected
(DO)
F
8 7
0 (Bit number)
SW00 + 0
Error code (I/O error = 2)
Subslot (function) number (= 1)
SW00 + 1
Not used.
SW00 + 2
Not used.
SW00 + 3
Not used.
SW00 + 4
Not used.
SW00 + 5
Not used.
SW00 + 6
Not used.
SW00 + 7
Not used.