Cpu unit/cpu module error status – Yaskawa MP3200 Troubleshooting Manual User Manual
Page 144

7.5 System Register Configuration and Error Status
Error Status for Individual Products
7-18
CPU Unit/CPU Module Error Status
The following table lists the registers that are related to errors in the CPU Unit/CPU Module.
The CPU Unit/CPU Module error status is illustrated in the following figure.
* SW00215 is not used by the MP3300.
Name
Register
Addresses
Remarks
I/O Error Count
SW00200
Number of I/O error occurrences
Input Error Count
SW00201
Number of input error occurrences
Input Error Address
SW00202
Latest input error address (register address in
IW)
Output Error Count
SW00203
Number of output error occurrences
Output Error Address
SW00204
Latest output error address (register address in
OW)
Reserved for system.
SW00205
Not used.
SW00206
SW00207
I/O Error Status
SW00208 to
SW00217
CPU Unit/CPU Module Error Status
SW00218 to
SW00223
Reserved for system.
SW00224 to
SW00231
Error status of Slot 1 (Depends on the Modules that
are mounted and the error code.)
(218IFD)
F
8 7
0 (Bit number)
SW00208
Status
Subslot (function) number (= 2)
1
0
(Bit number)
SW00209
···························
Write
Read
F
C B
8 7
4 3
0 (Bit number)
SW00210
Write transmission ST Reserved for system. Read transmission ST Reserved for system.
SW00211
Not used.
SW00212
Not used.
F
8 7
0
SW00213
Error code (station error = 1)
Subslot (function) number (= 3)
F
2
1
0
SW00214
ST#15
···························
ST#2
ST#1
Not used.
F
E
D
SW00215* Not used.
ST#30
ST#29
···························
ST#17
ST#16
SW00216
Not used.
SW00217
Not used.
SVC,
SVC32
218IFD