Module information, Module information -36, Configuration – Yaskawa MP3200 Troubleshooting Manual User Manual
Page 162: Cpu unit/cpu module optional modules

7.5 System Register Configuration and Error Status
Module Information
7-36
Module Information
The data in these registers give hardware information on the Units and Modules that are used in the
Machine Controller.
Configuration
CPU Unit/CPU Module
Optional Modules
Name
Register Addresses
Remarks
CPU Unit Information
SW00800
CPU Unit ID/CPU Module ID
SW00801
Hardware version (BCD)
SW00802
Software version (BCD)
SW00803
Number of subslots (hex)
SW00804
Function Module 1 ID (hex)
SW00805
Function Module 1 Status
SW00806
Function Module 2 ID (hex)
SW00807
Function Module 2 Status
SW00808
Function Module 3 ID (hex)
SW00809
Function Module 3 Status
SW00810
Function Module 4 ID (hex)
SW00811
Function Module 4 Status
SW00812
Function Module 5 ID (hex)
SW00813
Function Module 5 Status
SW00814
Function Module 6 ID (hex)
SW00815
Function Module 6 Status
Optional Module Informa-
tion
SW00816 to
SW01095
Optional Module information
(Depends on CPU Unit model and mounted Optional Mod-
ules.)
Name
Register Address
Remarks
Module Infor-
mation
SW00 + 0
Optional Module ID
SW00 + 1
Hardware version (BCD)
SW00 + 2
Software version (BCD)
SW00 + 3
Number of sub-slots (hex)
SW00 + 4
ID of Function Module 1 (hex)
SW00 + 5
Status of Function Module 1
SW00 + 6
ID of Function Module 2 (hex)
SW00 + 7
Status of Function Module 2