7.5 System Register Configuration and Error Status
Module Information
7-37
T
roubleshooting System Errors
Function Module Status Details
CPU Unit/CPU Module Information
CPU-201, CPU-202, or CPU-301
Value
Text Displayed in MPE720
Module Configuration Definition
Status
0
None
There is no Module Definition and the Module is not mounted.
1
Empty
There is a Module Definition, but the Module is not mounted.
2
Operating (Driving)
The Module is operating normally.
3
Standby (Reserved for system.)
The Module is on standby.
4
Failure
An error was detected in the Module.
5
× Module name
The mounted Module does not match the definition.
6
Waiting for initialization
The Module is mounted, but there is no Detailed Function Module
Definition.
7
Driving Stop
Local I/O is stopped.
8 to
−
Reserved for system.
Name
Register
Addresses
Remarks
CPU Unit Information
SW00800
CPU Unit ID/CPU Module ID
SW00801
Hardware version (BCD)
SW00802
Software version (BCD)
SW00803
Number of sub-slots (hex)
SW00804
Function Module 1 ID (hex)
SW00805
Function Module 1 Status
SW00806
Function Module 2 ID (hex)
SW00807
Function Module 2 Status
SW00808
Function Module 3 ID (hex)
SW00809
Function Module 3 Status
SW00810
Function Module 4 ID (hex)
SW00811
Function Module 4 Status
SW00812
Function Module 5 ID (hex)
SW00813
Function Module 5 Status
SW00814
Function Module 6 ID (hex)
SW00815
Function Module 6 Status
Continued on next page.