7.5 System Register Configuration and Error Status
Automatic Reception Status (Ethernet Communications)
7-80
Transmission Status
Error Status
Circuit
Number 8
CH3 Status
SW25608 to SW25615
Same as CH1 status
CH4 Status
SW25616 to SW25623
Same as CH1 status
CH5 Status
SW25624 to SW25631
Same as CH1 status
CH6 Status
SW25632 to SW25639
Same as CH1 status
CH7 Status
SW25640 to SW25647
Same as CH1 status
CH8 Status
SW25648 to SW25655
Same as CH1 status
CH9 Status
SW25656 to SW25663
Same as CH1 status
CH10 Status
SW25664 to SW25671
Same as CH1 status
Register Value
Status
Description
0
−
Unused connection.
1
IDLE
Standby mode for executing message functions.
2
WAIT
Waiting to establish a connection.
3
CONNECT
Ready to send and receive data.
Register Value
Status
Description
0
No error
Normal
1
Socket creation error
System error
2
Local port number error
Local port number setting error (The same address is
bound during disconnection of the TCP connection.)
3
Changing socket attribute error
System error (for TCP)
4
Connection Error (M-SND)
Connection error (The connection was rejected by the
remote station when establishing a connection with an
unpassive open for TCP.)
5
Connection error (M-RCV)
Connection error (With a passive open for TCP)
6
System error
System error
7
TCP data send error
Data sending error (The remote station does not exist or
has not started when using TCP.)
8
UDP data send error
Data sending error (for UDP)
9
TCP data receive error
Data reception error (The MP3000 received a request to
disconnect from the remote station for TCP.)
10
UDP data receive error
Data reception error (for UDP)
11
Changing socket option error
System error
12
Data conversion error
Data conversion error
Continued from previous page.
Circuit Number
Name
Register Addresses
Name