Wiring Control Circuit Terminals

2-

25

Relay

outputs

MA

Fault output signal

(NO contact)

MA / MC: Closed during fault condition

MB / MC: Open during fault condition

Form C

Dry contacts

capacity:

1 A max. at 250 Vac

1 A max. at 30 Vdc

MB

Fault output signal

(NC contact)

MC

Relay contact output

common

-

M1

Multi-function contact

output

(NO contact)

Factory setting: Operating

Operating when CLOSED across M1 and

M2.

Multi-

function

digital

output.

Function

set by

H2-01

Form A

Dry contacts

capacity:

1 A max. at 250 Vac

1 A max. at 30 Vdc

M2

M3

Multi-function contact

output 2

Factory setting: Zero speed

Zero speed level (b2-01) or below when

CLOSED.

Multi-

function

digital

output.

Function

set by

H2-02

M4

M5

Multi-function contact

output 3

Factory setting: Frequency

agreement detection

Frequency within 2 Hz of set

frequency when CLOSED.

Multi-

function

digital

output.

Function

set by

H2-03

M6

Analog

monitor

outputs

FM

Multi-function analog

monitor 1

0 to +10Vdc / 100% frequency

-10 to +10Vdc / 100% frequency

4 to 20mA / 100% frequency

Multi-

function

analog

output 1.
Function

set by

H4-01

0 to +10 Vdc ±5%

2 mA max.

AM

Multi-function analog

monitor 2

0 to +10Vdc / 100% Drive's rated

output current

-10 to +10Vdc / 100% Drive's rated output

current

4 to 20mA / 100% Drive's rated output cur-

rent

Multi-

function

analog

output 2.
Function

set by

H4-04

AC

Analog common

-

Pulse

I/O

RP

Multi-function pulse input

*3

Factory setting: Frequency reference

Function

set by

H6-01

0 to 32 kHz (3 k

Ω)

MP

Multi-function pulse

monitor

Factory setting: Output frequency

Function

set by

H6-06

0 to 32 kHz (2.2 k

Ω)

Table 2.10 Control Circuit Terminals (Continued)

Type

No.

Signal Name

Function

Signal Level