Input Terminal Functions

6-

69

Input Terminal Functions

This section explains input terminal functions, which set operating methods by switching functions for the
multi-function contact input terminals (S3 to S12).

‹

Temporarily Switching Operation between Digital Operator and Control
Circuit Terminals

You can switch the Drive run command inputs and frequency reference inputs between local (i.e., Digital
Operator) and remote (input method using b1-01 and b1-02).

You can switch between local and remote by turning ON and OFF the terminals if an output from H1-01 to
H1-10 (multi-function contact input terminal S3 to S12 function selection) has been set to 1 (local/remote
selection).

To set the control circuit terminals to remote, set b1-01 and b1-02 to 1 (Control circuit terminals).

„

Related Parameters

Parameter

Number

Name

Description

Setting
Range

Factory

Setting

Change

during

Operation

Control Methods

Display

V/f

V/f

with

PG

Open

Loop

Vector

1

Flux

Vector

Open

Loop

Vector

2

b1-01

Frequency
Reference
Selection

Selects the frequency reference
input source.
0: Operator - Digital preset speed

U1-01 or d1-01 to d1-17.

1: Terminals - Analog input

terminal A1 (or terminal A2
based on parameter H3-09).

2: Serial Com - Modbus RS-422/

485 terminals R+, R-,

S+, and S-.
3: Option PCB - Option board

connected on 2CN.

4: Pulse Input (Terminal RP)

0 to 4

1

No

Q

Q

Q

Q

Q

Reference
Source

b1-02

Run
Command
Selection

Selects the run command input
source.
0: Operator - RUN and STOP

keys on Digital Operator.

1: Terminals - Contact closure on

terminals S1 or S2.

2: Serial Com - Modbus RS-422/

485 terminals R+, R-,

S+, and S-.
3: Option PCB - Option board

connected on 2CN.

0 to 3

1

No

Q

Q

Q

Q

Q

Run Source

INFO

You can also perform local/remote switching using the LOCAL/REMOTE Key on the Digital Operator. When
the local/remote function has been set in the external terminals, the LOCAL/REMOTE Key function on the
Digital Operator will be disabled.