Application Parameters: b

The following settings are made with the application parameters (B parameters): Operation method selection,
DC injection braking, speed searching, timer functions, dwell functions, and energy saving functions.

„

Operation Mode Selections: b1

User parameters for operation mode selection are shown in the following table.

Parameter

Number

Name

Description

Setting

Range

Factory

Setting

Change

during

Operation

Control Methods

MODBUS

Register

Display

V/f

V/f

with

PG

Open

Loop

Vector

1

Flux

Vector

Open

Loop

Vector

2

b1-01

Frequency
Reference
Selection

Selects the frequency
reference input source.
0: Operator - Digital preset

speed U1-01 or d1-01 to
d1-17.

1: Terminals - Analog input

terminal A1 (or terminal
A2 based on parameter
H3-09).

2: Serial Com - Modbus

RS-422/485 terminals R+,
R-, S+, and S-.

3: Option PCB - Option board

connected on 2CN.

4: Pulse Input (Terminal RP)

0 to 4

1

No

Q

Q

Q

Q

Q

180H

Reference
Source

b1-02

Run
Command
Selection

Selects the run command
input source.
0: Operator - RUN and STOP

keys on Digital Operator.

1: Terminals - Contact closure

on terminals S1 or S2.

2: Serial Com - Modbus RS-

422/485 terminals R+, R-,
S+, and S-.

3: Option PCB - Option board

connected on 2CN.

0 to 3

1

No

Q

Q

Q

Q

Q

181H

Run Source

b1-03

Stopping
Method
Selection

Selects the stopping method
when the run command is
removed.
0: Ramp to Stop
1: Coast to Stop
2: DC Injection to Stop
3: Coast with Timer (A new

run command is ignored if
received before the timer
expires).

0 to 3

*

0

No

Q

Q

Q

Q

Q

182H

Stopping
Method

b1-04

Reverse
Operation
Selection

Determines the forward

rotation of the motor, and if
reverse operation is disabled.

0: Reverse enabled
1: Reverse disabled

0 or 1

0

No

A

A

A

A

A

183H

Reverse
Oper