-30

„

Reference Limits: d2

User parameters for frequency reference limits are shown in the following table.

„

Jump Frequencies: d3

User parameters for jump frequencies are shown in the following table.

Parameter

Number

Name

Description

Setting

Range

Factory

Setting

Change

during

Operation

Control Methods

MODBUS

Register

Display

V/f

V/f

with

PG

Open

Loop

Vector

1

Flux

Vector

Open

Loop

Vector

2

d2-01

Frequency
Reference
Upper Limit

Determines maximum
frequency reference, set as a
percentage of maximum
output frequency (E1-04). If
the frequency reference is
above this value, actual Drive
speed will be limited to this
value. This parameter applies to
all frequency reference sources.

0.0

to

110.0

100.0%

No

A

A

A

A

A

289H

Ref Upper
Limit

d2-02

Frequency
Reference
Lower Limit

Sets the output frequency
lower limit as a percentage of
the maximum output
frequency.

0.0

to

110.0

0.0%

No

A

A

A

A

A

28AH

Ref Lower
Limit

d2-03

Master Speed
Reference
Lower Limit

Set the master speed
reference lower limit as a
percent, taking the max.
output frequency to be 100%.

0.0

to

110.0

0.0%

No

A

A

A

A

A

293H

Ref1 Lower
Limit

Parameter

Number

Name

Description

Setting

Range

Factory

Setting

Change

during

Operation

Control Methods

MODBUS

Register

Display

V/f

V/f

with

PG

Open

Loop

Vector

1

Flux

Vector

Open

Loop

Vector

2

d3-01

Jump
Frequency 1

This parameter allow
programming of up to three
prohibited frequency
reference points for
eliminating problems with
resonant vibration of the
motor / machine. This feature
does not actually eliminate
the selected frequency values,
but will accelerate and
decelerate the motor through
the prohibited bandwidth.

0.0

to

400.0

0.0Hz

No

A

A

A

A

A

294H

Jump Freq 1

d3-02

Jump
Frequency 2

0.0Hz

No

A

A

A

A

A

295H

Jump Freq 2

d3-03

Jump
Frequency 3

0.0Hz

No

A

A

A

A

A

296H

Jump Freq 3

d3-04

Jump
Frequency
Width

This parameter determines
the width of the deadband
around each selected
prohibited frequency
reference point. A setting of
"1.0" will result in a
deadband of +/- 1.0Hz.

0.0

to

20.0

1.0Hz

No

A

A

A

A

A

297H

Jump
Bandwidth