Digital Operator Display Functions and Levels

5-

7

E1-04

Max.
Output
Frequency
(FMAX)

These parameters are only applicable
when V/f Pattern Selection is set to
Custom (E1-03 = F or FF). To set V/f
characteristics in a straight line, set the
same values for E1-07 and E1-09. In
this case, the setting for E1-08 will be
disregarded. Be sure that the four fre-
quencies are set in the following man-
ner or else an OPE10 fault will occur:

E1-04

≥ E1-11 ≥ E1-06 > E1-07 ≥ E1-09

Note: Setting parameter E1-01 to zero

is also acceptable.

40.0

to

400.0

*9

60.0Hz

*4

No

Q

Q

Q

Q

Q

303H

Max
Frequency

E1-05

Max.
Output
Voltage
(VMAX)

0.0

to

255.0

*3

230.0 V

*3*4

No

Q

Q

Q

Q

Q

304H

Max
Voltage

E1-06

Base
Frequency
(FA)

0.0

to

400.0

*9

60.0Hz

*4

No

Q

Q

Q

Q

Q

305H

Base
Frequency

E1-09

Min.
Output
Frequency
(FMIN)

0.0

to

400.0

*9

0.5Hz

*4

No

Q

Q

Q

A

Q

308H

Min
Frequency

E1-13

Base
Voltage
(VBASE)

Set only when the V/F pattern is finely
adjusted in the constant power (HP)
area above base speed. Adjustment is
not normally required. If E1-13 = 0.0,
then value in E1-05 is used for E1-13.
Auto-Tuning sets this value.

0.0

to

255.0

(240V)

*3

0.0 V

*5

No

A

A

Q

Q

Q

30CH

Base
Voltage

E2-01

Motor
Rated
Current

Sets the motor nameplate full load
current in amperes (A). This value is
automatically set during Auto-Tuning.

0.32

to

6.40

*7

1.90 A

*6

No

Q

Q

Q

Q

Q

30EH

Motor
Rated FLA

E2-04

Number of
Motor
Poles

Sets the number of motor poles. This
value is automatically set during
Autotuning.

2 to 48

4

No

No

Q

No

Q

Q

311H

Number of
Poles

E2-11

Motor
Rated
Output

Sets the motor rated power in kilowatts
(kW). This value is automatically set
during Auto-Tuning. 1HP = 0.746kW

0.00

to

650.000

0.40

*10

No

Q

Q

Q

Q

Q

318H

Mtr Rated
Power

F1-01

PG
Parameter

Sets the number of pulses per revolu-
tion of the encoder (pulse generator).
(Do not set as a multiple.)

0

to

60000

600

No

No

Q

No

Q

No

380H

PG
Pulses/Rev

Parameter

Number

Name

Description

Setting

Range

Factory

Setting

Change

during

Operation

Control Methods

MODBUS
Register

Display

V/f

V/f

with

PG

Open

-loop

Vector

1

Flux

Vector

Open

Loop

Vector

2