Individual Functions

6-

99

„

Related Parameters

Parameter

Number

Name

Description

Setting
Range

Factory

Setting

Change

during

Operation

Control Methods

Display

V/f

V/f

with

PG

Open

Loop

Vector

1

Flux

Vector

Open

Loop

Vector

2

b5-01

PID Function
Setting

This parameter determines the

function of the PID control.

0: Disabled
1: D= Feedback
2: D= Feed-Forward
3: Freq. Ref. + PID output
(D = Feedback)
4: Freq. Ref. + PID output
(D = Feed-Forward)

0 to 4

0

No

A

A

A

A

A

PID Mode

b5-02

Proportional
Gain Setting

Sets the proportional gain of the
PID controller.

0.00

to

25.00

1.00

Yes

A

A

A

A

A

PID Gain

b5-03

Intregral Time
Setting

Sets the integral time for the PID
controller. A setting of zero
disables integral control.

0.0

to

360.0

1.0sec

Yes

A

A

A

A

A

PID I Time

b5-04

Intregral Limit
Setting

Sets the maximum output possible
from the integrator. Set as a
percentage (%) of maximum
frequency.

0.0

to

100.0

100.0%

Yes

A

A

A

A

A

PID I Limit

b5-05

Derivative
Time

Sets D control derivative time. A
setting of 0.00 disables derivative
control.

0.00

to

10.00

0.00sec

Yes

A

A

A

A

A

PID D Time

b5-06

PID Output
Limit

Sets the maximum output possible
from the entire PID controller. Set
as a percentage (%) of maximum
frequency.

0.0

to

100.0

100.0%

Yes

A

A

A

A

A

PID Limit

b5-07

PID Offset
Adjustment

Sets the amount of offset of the
output of the PID controller. Set
as a percentage (%) of maximum
frequency.
The offset is summed with the
PID output. This can be used to
artificially kick-start a slow
starting PID loop.

-100.0

to

+100.0

0.0%

Yes

A

A

A

A

A

PID Offset

b5-08

PID Primary
Delay Time
Constant

Sets the amount of time for the
filter on the output of the PID
controller.
Note: The offset is summed with
the PID output. This can be used
to artifically kick-start a slow
starting PID loop.
Note: Normally , change is not
required.

0.00

to

10.00

0.00sec

Yes

A

A

A

A

A

PID Delay
Time

b5-09

PID Output
Level Selection

Determines whether the PID

controller will be direct or
reverse acting.

0: Normal Output (direct acting)
1: Reverse Output (reverse

acting)

0 to 1

0

No

A

A

A

A

A

Output Level
Sel