beautypg.com

Setting a password, Related parameters, Setting precautions – Yaskawa G7 Drive User Manual

Page 366: Displaying user-set parameters only, Setting a password -149, Displaying user-set parameters only -149, Related parameters „ setting precautions

background image

Digital Operator Functions

6-

149

‹

Setting a Password

When a password is set in A1-05, if the set values in A1-04 and A1-05 do not match, you cannot refer to or
change the settings of parameters A1-01 to A1-03, or A2-01 to A2-32.

You can prohibit the setting and referencing of all parameters except A1-00 by using the password function in
combination with setting A1-01 to 0 (Monitor only).

„

Related Parameters

„

Setting Precautions

Parameter A1-05 cannot be displayed using normal key operations. To display A1-05, hold down the RESET
Key and press the MENU Key while A1-04 is displayed.

‹

Displaying User-set Parameters Only

You can set and refer to parameters necessary to the Drive only, using the A2 parameters (user-set parameters)
and A1-01 (Parameters Access Level).

Set the number of the parameter to which you want to refer in A2-01 to A2-32, and then set A1-01 to 1. You
can set and refer to parameters set in A1-01 to A1-03 and A2-01 to A2-32 only, using advanced programming
mode.

Parameter

Number

Name

Description

Setting
Range

Factory

Setting

Change

during

Operation

Control Methods

Display

V/f

V/f

with

PG

Open

Loop

Vector

1

Flux

Vector

Open

Loop

Vector

2

A1-01

Access Level
Selection

Selects which parameters are

accessible via the Digital
Operator.

0: Operation Only
1: User Level (only available if

A2 parameters have been set)

2: Advanced Level

0 to 2

2

Yes

A

A

A

A

A

Access Level

A1-04

Password 1

When the value set into A1-04
does NOT match the value set into
A1-05, parameters A1-01 thru A1-
03 and A2-01 thru A2-32 cannot
be changed. All other parameters
as determined by A1-01 can be
changed. Parameter A1-05 can be
accessed by pressing the MENU
key while holding the RESET key.

0

to

9999

0

No

A

A

A

A

A

Enter
Password

A1-05

Password 2

When the value set into A1-04
does NOT match the value set into
A1-05, parameters A1-01 thru A1-
03 and A2-01 thru A2-32 cannot
be changed. All other parameters
as determined by A1-01 can be
changed. Parameter A1-05 can be
accessed by pressing the MENU
key while holding the RESET key.

0

to

9999

0

No

A

A

A

A

A

Select
Password