Individual Functions

6-

137

Multi-function Contact Input Functions (H1-01 to H1-10)

Multi-function Contact Output Functions (H2-01 to H2-03)

To output the zero-servo status externally, assign the Zero Servo End signal (setting 33) to one of the multi-
function outputs (H2-01 to H2-03).

Monitor Function

Setting

Value

Function

Control Methods

V/f

V/f

with

PG

Open

Loop

Vector

1

Flux

Vector

Open

Loop

Vector

2

72

Zero-servo command (ON: Zero-servo)

No

No

No

Yes

No

Setting

Value

Function

Control Methods

V/f

V/f

with

PG

Open

Loop

Vector

1

Flux

Vector

Open

Loop

Vector

2

33

Zero-servo end
ON: Current position is within zero-servo start position ± the zero-servo end width.

No

No

No

Yes

No

Parameter

Number

Name

Description

Output Signal Level During

Multi-Function

Analog Output

Min.

Unit

Control Methods

Display

V/f

V/f

with

PG

Open

Loop

Vector

1

Flux

Vector

Open

Loop

Vector

2

U1-35

Zero-servo
movement
pulses

Shows the number of PG pulses
times 4 for the movement range
when stopped at zero.

(Cannot be output.)

1

No

No

No

A

No

Zero Servo
Pulse