Options

6-

153

* Factory setting will change according to the control mode (factory settings for Vector Control w/PG are shown here).

„

Using PG Speed Control Card

There are four types of PG Speed Control Card that can be used in V/f control with PG.

PG-A2: A-phase (single) pulse input, compatible with open collector or complimentary outputs.

PG-B2: A/B-phase pulse input, compatible with complimentary outputs.

PG-D2: A-phase (single) pulse input, compatible with line drivers.

PG-X2: A/B/Z-phase pulse input, compatible with line drivers.

There are two types of PG Speed Control Cards that can be used for flux vector control.

PG-B2: A/B phase pulse inputs, complementary outputs

PG-X2: A/B/Z phase pulse inputs, line driver outputs

For the connection diagram, refer to page 2-36.

„

Setting Number of PG Pulses

Set the number of PG (Pulse Generator/Encoder) pulses in pulses/rotation. Set the number of A-phase or B-
phase pulses per 1 motor rotation in F1-01.

„

Matching PG Rotation Direction and Motor Rotation Direction

Parameter F1-05 matches the PG rotation direction and the motor rotation direction. If the motor is rotating
forwards, set whether it is A-phase driven or B-phase driven. Make this setting when using PG-B2 or PG-X2.

F1-12

Number of PG
Gear Teeth 1

Sets the gear ratio between the
motor shaft and the encoder (PG).

A gear ratio of 1 will be used if
either of these parameters is set to
0. This function is not available in
flux vector control.

0

to

1000

0

No

No

A

No

No

No

PG # Gear
Teeth1

F1-13

Number of PG
Gear Teeth 2

0

No

No

A

No

No

No

PG # Gear
Teeth2

F1-14

PG Open-Cir-
cuit Detection
Time

Configures the PG open (PGO)
function. PGO will be detected if
no PG pulses are detected for a
time longer than F1-14. See
F1-02.

0.0

to

10.0

2.0sec

No

No

A

No

A

No

PGO Detect
Time

Parameter

Number

Name

Description

Setting

Range

Factory

Setting

Change

during

Operation

Control Methods

Display

V/f

V/f

with

PG

Open

Loop

Vector

1

Flux

Vector

Open

Loop

Vector

2