beautypg.com

Reference detection: l4 – Yaskawa G7 Drive User Manual

Page 177

background image

5

-66

„

Reference Detection: L4

User parameters for the reference detection function are shown in the following table.

Parameter

Number

Name

Description

Setting

Range

Factory

Setting

Change

during

Operation

Control Methods

MODBUS

Register

Display

V/f

V/f

with

PG

Open

Loop

Vector

1

Flux

Vector

Open

Loop

Vector

2

L4-01

Speed
Agreement
Detection
Level

These parameters configure the
multi-function output (H2-oo)
settings "Fref/Fout Agree 1",
"Fref/Set Agree 1", "Frequency
Detection 1," and "Frequency
detection 2". Parameter L4-01
sets the level while parameter
L4-02 sets the hysteresis for the
Speed Detection Output
Function.

0.0

to

400.0

0.0Hz

No

A

A

A

A

A

499H

Spd Agree
Level

L4-02

Speed
Agreement
Detection
Width

These parameters configure the
multi-function output (H2-oo)
settings "Fref/Fout Agree 1",
"Fref/Set Agree 1", "Frequency
Detection 1," and "Frequency
detection 2". Parameter L4-01
sets the level while parameter
L4-02 sets the hysteresis for the
Speed Detection Output
Function.

0.0

to

20.0

2.0Hz

No

A

A

A

A

A

49AH

Spd Agree
Width

L4-03

Speed
Agreement
Detection
Level (+/-)

These parameters configure the
Multi-Function Output (H2-oo)
settings "Fref/Fout Agree 2",
"Fref/Set Agree 2", "Frequency
Detection 3," or "Frequency
Detection 4". Parameter L4-03
sets the level while parameter
L4-04 sets the hysteresis for the
Speed Detection Output
Function.

-400.0

to

+400.0

0.0Hz

No

A

A

A

A

A

49BH

Spd Agree
Lvl+-

L4-04

Speed
Agreement
Detection
Width (+/-)

These parameters configure the
Multi-Function Output (H2-oo)
settings "Fref/Fout Agree 2",
"Fref/Set Agree 2", "Frequency
Detection 3," or "Frequency
Detection 4". Parameter L4-03
sets the level while parameter
L4-04 sets the hysteresis for the
Speed Detection Output
Function.

0.0

to

20.0

2.0Hz

No

A

A

A

A

A

49CH

Spd Agree
Wdth+-

L4-05

Frequency
Reference
Loss
Detection
Selection

Determines how the Drive will
react when the frequency
reference is lost. The frequency
reference is considered lost
when reference drops 90% or
more of its current value for
400ms.
0: Stop - Drive will stop.
1: Run at L4-06 PrevRef -

Drive will run at the
percentage set in L4-06 of the
frequency reference level at
the time frequency reference
was lost.

0 to 1

0

No

A

A

A

A

A

49DH

Ref Loss
Sel