Stopping Methods

6-

9

Stopping Methods

This section explains methods of stopping the Drive.

‹

Selecting the Stopping Method when a Stop Command is Sent

There are four methods of stopping the Drive when a stop command is sent:

Deceleration to stop

Coast to stop

DC braking stop

Coast to stop with timer

Set parameter b1-03 to select the Drive stopping method. A DC braking stop and coasting to a stop with a
timer cannot be set for flux vector control.

„

Related Parameters

Parameter

Number

Name

Description

Setting
Range

Factory

Setting

Change

during

Operation

Control Methods

Display

V/f

V/f

with

PG

Open-

Loop

Vector

1

Flux

Vector

Open

Loop

Vector

2

b1-03

Stopping
Method
Selection

Selects the stopping method when the

run command is removed.

0: Ramp to Stop
1: Coast to Stop
2: DC Injection to Stop
3: Coast with Timer (A new run

command is ignored if received
before the timer expires).

0 to 3

*

0

No

Q

Q

Q

Q

Q

Stopping
Method

b1-05

Minimum
Output
Frequency
(E1-09) or
Less
Operation
Selection

Operation method when frequency
reference is less than minimum output

frequency set in E1-09.

0: Operates according to frequency

reference (E1-09 is disabled).

1: Output shuts off (coast to stop if less

than E1-09).

2: Operates according to E1-09

(frequency reference set to E1-09).

3: Zero speed (frequency reference

becomes zero when less than E1-09).

0 to 3

0

No

No

No

No

A

No

Zero-Speed
Oper

b2-01

DC
Injection
Braking
Start
Frequency

Sets the frequency at which DC injection
braking starts when ramp to stop
(b1-03 = 0) is selected. If b2-01< E1-09,
DC Injection braking starts at E1-09.
Note: Zero Speed restrictions are active
in Flux Vector Mode.

0.0 to

10.0

0.5Hz

No

A

A

A

A

A

DCInj Start
Freq