beautypg.com

Yaskawa G7 Drive User Manual

Page 392

background image

Protective and Diagnostic Functions

7-

11

EF3

(blinking)

Ext Fault

S3

External fault (Input terminal S3)

An external fault was input from a
multi-function input terminal (S3 to
S12).

• Reset external fault inputs to the

multi-function inputs.

• Remove the cause of the external

fault.

EF4

(blinking)

Ext Fault

S4

External fault (Input terminal S4)

EF5

(blinking)

Ext Fault

S5

External fault (Input terminal S5)

EF6

(blinking)

Ext Fault

S6

External fault (Input terminal S6)

EF7

(blinking)

Ext Fault

S7

External fault (Input terminal S7)

EF8

(blinking)

Ext Fault

S8

External fault (Input terminal S8)

EF9

(blinking)

Ext Fault

S9

External fault (Input terminal S9)

EF10

(blinking)

Ext Fault

S10

External fault (Input terminal S10)

EF11

(blinking)

Ext Fault

S11

External fault (Input terminal S11)

EF12

(blinking)

Ext Fault

S12

External fault (Input terminal S12)

FBL

(blinking)

Feed-

back
Loss

PID Feedback Reference Lost
A PID feedback reference loss was
detected (b5-12 = 2) and the PID feed-
back input was less than b5-13 (PID
feedback loss detection level) for
longer than the time set in b5-14 (PID
feedback loss detection time).

-

-

Table 7.2 Alarm Displays and Processing (Continued)

Display

Meaning

Probable causes

Corrective Actions