beautypg.com

Yaskawa G7 Drive User Manual

Page 391

background image

7

-10

OL3

(blinking)

Over-

torque

Det 1

Overtorque 1
There has been a current greater than
the setting in L6-02 for longer than the
setting in L6-03.

-

• Make sure that the settings in L6-02

and L6-03 are appropriate.

• Check the mechanical system and

correct the cause of the overtorque.

OL4

(blinking)

Over-

torque

Det 2

Overtorque 2
There has been a current greater than
the setting in L6-05 for longer than the
setting in L6-06.

-

• Make sure that the current setting in

L6-05 and time setting in L6-06 are
appropriate.

• Check the mechanical system and

correct the cause of the overtorque.

UL3

(blinking)

Under-

torq Det

1

Undertorque 1
There has been a current less than the
setting in L6-02 for longer than the
setting in L6-03.

-

• Make sure that the settings in L6-02

and L6-03 are appropriate.

• Check the mechanical system and

correct the cause of the overtorque.

UL4

(blinking)

Under-

torq Det

2

Undertorque 2
There has been a current less than the
setting in L6-05 for longer than the
setting in L6-06.

-

• Make sure that the current setting in

L6-05 and time setting in L6-06 are
appropriate.

• Check the mechanical system and

correct the cause of the overtorque.

OS

(blinking)

Over-
speed

Det

Overspeed
The speed has been greater than the
setting in F1-08 for longer than the
setting in F1-09.

Overshooting/undershooting are
occurring.

Adjust the gain again.

The reference speed is too high.

Check the reference circuit and refer-
ence gain.

The settings in F1-08 and F1-09 aren't
appropriate.

Check the settings in F1-08 and F1-09.

PGO

(blinking)

PG Open

The PG is disconnected
The Drive is outputting a frequency,
but PG pulses aren't being input.

There is a break in the PG wiring.

Fix the broken/disconnected wiring.

The PG is wired incorrectly.

Fix the wiring.

Power isn't being supplied to the PG.

Supply power to the PG properly.

DEV

(blinking)

Speed

Devia-

tion

Excessive Speed Deviation
The speed deviation has been greater
than the setting in F1-10 for longer
than the setting in F1-11.

The load is too large.

Reduce the load.

The acceleration time and decelera-
tion time are too short.

Lengthen the acceleration time and
deceleration time.

The load is locked.

Check the mechanical system.

The settings in F1-10 and F1-11 aren't
appropriate.

Check the settings in F1-10 and F1-11.

EF0

Opt

External

Flt

External fault detected for Commu-
nications Card other than SI-K2
Continuing operation was specified
for EF0 (F6-03 = 3)and an external
fault was input from the Option Card.

-

Remove the cause of the external fault.

Table 7.2 Alarm Displays and Processing (Continued)

Display

Meaning

Probable causes

Corrective Actions