5

-38

* 1. These are values for a 200-240V class Drive. Values for a 380-480V class Drive are double.
* 2. The factory setting will change when the control method is changed. (V/f control factory settings are given.)
* 3. The setting range is 0 to 66.0 for open-loop vector control 2.

E3-02

Motor 2
Maximum
Output
Frequency
(FMAX)

To set V/f characteristics in a straight
line, set the same values for E3-05
and E3-07.
In this case, the setting for E3-06 will
be disregarded.
Always ensure that the four frequen-
cies are set in the following manner
or else an OPE10 fault will occur:
E3-02 (FMAX)

≥ E3-04 (FA) ≥

E3-05 (FB)

≥ E3-07 (FMIN)

40.0

to

400.0

*3

60.0Hz

No

A

A

A

A

A

31AH

Max
Frequency

E3-03

Motor 2
Maximum
Output Volt-
age
(VMAX)

0.0

to

255.0

(240V)

0.0

to

510.0

(480V)

230.0V

or

460.0V

*2

No

A

A

A

A

A

31BH

Max
Voltage

E3-04

Motor 2
Base
Frequency
(FA)

0.0

to

400.0

60.0Hz

No

A

A

A

A

A

31CH

Base
Frequency

E3-05

Motor 2
Mid.
Output
Frequency 1
(FB)

0.0

to

400.0

3.0Hz

*2

No

A

A

A

No

No

31DH

Mid
Frequency

E3-06

Motor 2
Mid.
Output Volt-
age 1 (VA)

0.0

to

255.0

(240V)

0.0

to

510.0

(480V)

12.6

Vac

or

25.3

Vac

*1

No

A

A

A

No

No

31EH

Mid
Voltage

E3-07

Motor 2
Minimum
Output
Frequency
(FMIN)

0.0

to

400.0

0.5Hz

*2

No

A

A

A

A

A

31FH

Min
Frequency

E3-08

Motor 2
Minimum
Output
Voltage
(VMIN)

0.0

to

255.0

(240V)

0.0

to

510.0

(480V)

2.3 Vac

or

4.6 Vac

*1

No

A

A

A

No

No

320H

Min
Voltage

Parameter

Number

Name

Description

Setting

Range

Factory

Setting

Change

during

Operation

Control Methods

MODBUS

Register

Display

V/f

V/f

with

PG

Open

Loop

Vector

1

Flux

Vector

Open

Loop

Vector

2

Output voltage (V)

Frequency (Hz)