-8

Performing Operations Using a 3-wire Sequence

When any parameter from H1-01 to H1-10 (multi-function contact input terminals S3 to S12) is set to 0, ter-
minals S1 and S2 are used for a 3-wire sequence, and the multi-function input terminal that has been set func-
tions as a forward/reverse run command terminal.

When the Drive is initialized for 3-wire sequence control with A1-03, multi-function input 3 becomes the
input terminal for the forward/reverse run command.

Fig 6.9 3-wire Sequence Wiring Example

Fig 6.10 Three-wire Sequence Time Chart

INFO

Use a sequence that turns ON terminal S1 for 50ms or longer for the run command. This will make the run
command self-holding in the Drive.

Stop switch
(NC contact)

Operation switch
(NO contact)

Run command
(operates when ON)
Stop command
(stopped when ON)

Forward/reverse command
(multi-function input)

Sequence input common

50ms min.

Run command

Forward/reverse
command

Motor speed

Can be either ON or OFF

OFF

(stopped)

OFF (forward)

ON (reverse)

Stop

Forward

Reverse

Stop

Forward

Stop command