Machine Protection

6-

41

With vector control, the carrier frequency is fixed to the Carrier Frequency Upper Limit in C6-03 if user-
set or by the carrier frequency set in C6-02.

To fix the carrier frequency, set C6-03 and C6-04 to the same value, or set C6-05 to 0.

If the settings are as shown below, OPE11 (Parameter setting error) will occur.
If Carrier Frequency Proportional Gain (C6-05) > 6 and C6-03 < C6-04.

Depending on the carrier frequency setting, the Drive’s overload level may be reduced. Even when the
overload current falls to below 150%, OL2 (Drive overload) will be detected. The Drive overload current
reduction level is shown below.

Fig 6.33 Overload Reduction Level for V/f Control, V/f Control with PG, Open-loop Vector Control 1,

and Flux Vector Control

Fig 6.34 Overload Reduction Level for Open-loop Vector Control 2

100%

15kH z

0

50%

80%

200V 級22kW

10kH z

200-240 V, 22 kW

Carrier frequency

Overload reduction level

100%

8kHz

0

50%

4kHz

87%

200-240 V, 30 to 75 kW

Overload reduction level

Carrier frequency