Table A1-1. J7 Parameters - Continued

PARAM-

SETTING RANGE

SETTING

FACTORY

USER

PARA.

ETER

NAME

(AND UNITS)

INCREMENT

SETTING

SETTING

REF.

n21

Frequency Reference 1

6.0

n22

Frequency Reference 2

0.0

n23

Frequency Reference 3

0.1 (Hz)

0.0

n24

Frequency Reference 4

0.0 to 400

(< 100 Hz)

0.0

n25

Frequency Reference 5

or

0.0

5.11

n26

Frequency Reference 6

1 (Hz)

0.0

n27

Frequency Reference 7

(≥ 100 Hz)

0.0

n28

Frequency Reference 8

0.0

n29

Jog Frequency Reference

6.0

5.12

n30

Frequency Reference Upper

0 to 110

1 (%)

100

Limit

5.9

n31

Frequency Reference Lower

0 to 110

1 (%)

0

Limit

0.0 to 49.5

n32

Motor Rated Current

(Up to 120% of inverter rated current)

0.1 (A)

Note 1

5.24

0: Standard Motor

n33

Electronic Thermal Overload

1: Standard Motor - Short Term

1

0

Protection (for OL1 fault)

2: Disabled

5.24

n34

Electronic Thermal Overload

1 to 60

1 (min)

8

Protection Time Constant

0: Operates only when drive is running

n35

Cooling Fan Operation

(continues operation for 1 minute after

1

0

Selection

drive is stopped)

1: Operates with power applied to drive

0: Fwd / Rev command (3 wire control)

1

2

n36

Multi-function Input

[can only be set in n37]

(2)

Selection 2 (Terminal S2)

2: Reverse run (2 wire control)
3: External Fault (N.O.)

n37

Multi-function Input

4: External Fault (N.C.)

1

5

Selection 3 (Terminal S3)

5: Fault Reset

(0)

6: Multi-step speed ref. cmd. A

n38

Multi-function Input

7: Multi-step speed ref. cmd. B

1

3

Selection 4 (Terminal S4)

8: Multi-step speed ref. cmd. C

(3)

10: JOG Selection

n39

Multi-function Input

11: Accel/Decel time change cmd.

1

6

Selection 5 (Terminal S5)

12: External Base Block (N.O.)

(6)

5.17

13: External Base Block (N.C.)
14: Speed search from max. freq.
15: Speed search from set freq.
16: Accel/Decel hold command
17: Remote/Local selection
18: Serial Communication / control ckt.

selection

19: Fast Stop - Fault (N.O.)
20: Fast Stop - Alarm (N.O.)
21: Fast Stop - Fault (N.C.)
22: Fast Stop - Alarm (N.C.)
34: Up / Down command
35: Loop Test

[can only be set in n39]

Multi-Function Output

0: Fault

n40

Selection

1: During running

1

1

5.18

(Terminals MA, MB & MC)

2: Speed Agree
3: Zero Speed
4: Frequency detection 1
5: Frequency detection 2
6: Overtorque detection (N.O.)
7: Overtorque detection (N.C.)
10: Minor Fault
11: During Base Block
12: Local / Remote
13: Ready
14: During auto restart
15: During undervoltage
16: During reverse run
17: During speed search
18: Serial Comm. Controlled