Yaskawa J7 Drive User Manual

Page 77

background image

6-4

Fault Display

Digital

RUN (Green)

Drive

Explanation

Causes and

Operator

ALARM (Red)

Status

Corrective Actions

OC (Overcurrent)

• Short circuit or

Drive output current

grounding at drive

momentarily exceeds

output side

approx. 200% of rated

• Excessive load inertia

current.

• Extremely rapid accel/

decel time
(parameters n16 to n19)

• Special motor used
• Starting motor during

coasting

• Motor of a capacity

greater than the drive
rating has been started.

• Magnetic contactor

open/closed at the
drive output side

OV (Main circuit over-

• Insufficient decel time

Protective

voltage)

parameters n17 and n19)

Operation.

Main circuit DC voltage

• Lowering of minus load

Output is

exceeds the overvoltage

(elevator, etc.)

shut OFF

detection level because

and motor

of excessive regenerative

coasts to

energy from the motor.

• Increase decel time.

a stop.

Detection level:

• Connect optional dynamic

230V: Stops at main circuit

braking resistor.

DC voltage below
approx. 410V

460V: Stops at main circuit

DC voltage
approx. 820V or more

UV1 (Main circuit low

• Reduction of input

voltage)

power supply voltage

Main circuit DC voltage

• Open phase of input supply

drops below the low-

• Occurrence of momen-

voltage detection level

tary power loss

while the drive output
is ON.

230V: Stops at main circuit

Check the following:

DC voltage below

• Power supply voltage

approx. 200V

• Main circuit power

supply wiring is

460V: Stops at main circuit

connected.

DC voltage

• Terminal screws are

approx. 400V or more

securely tightened.

GF (Ground Fault)

Check motor insulation and

Ground current exceeded

wiring between drive and

drive rated current.

motor for damage.

Table 6-2. Fault Displays and Corrective Actions