15 momentary power loss ride-thru, Momentary power loss ride-thru -19 – Yaskawa J7 Drive User Manual
Page 54
5-19
n47 :
Momentary Power Loss Ride-thru
0
= Disabled (Factory setting)
Protection
1
= Enabled – 2 sec. power loss
ride-thru
2
= Enabled – indefinite power loss
ride-thru, provided control
power is maintained
The setting of this parameter either enables or disables the ride-thru feature of the Drive. If
disabled, the unit will stop immediately whenever a power loss occurs. If enabled, the Drive will
continue to operate during a momentary power loss of up to 80%, but if the loss exceeds the
identified time period, the Drive will stop.
5.15 MOMENTARY POWER LOSS RIDE-THRU
n44 :
Multi-function Analog Output
Factory setting:
0
The monitor output provides a 0-10 Vdc signal
proportional to either output frequency or output current
between terminals AM & AC:
0
= 0-10 Vdc proportional
to output frequency
1
= 0-10 Vdc proportional
to output current
n45 :
Analog Monitor Gain
Factory Setting:
1.00
Range: 0.01 to 2.00
This constant is used to calibrate the meter connected to terminals AM & AC.
Drive
AM
Analog
output
AC
(0-10 Vdc)
MULTI-
FUNCTION
MONITOR
OUTPUT
+ –
FREQUENCY/ CURRENT
METER
(1mA FULL SCALE)
5.16 MULTI-FUNCTION ANALOG MONITOR OUTPUT (Term. AM and AC)
n45
= 0.30
100%
MAX. OUTPUT
FREQUENCY
Factory Setting
OR CURRENT.
(
n45
= 1.00)
0
3 V
10 V
ANALOG OUTPUT