n47 :

Momentary Power Loss Ride-thru

0

= Disabled (Factory setting)

Protection

1

= Enabled – 2 sec. power loss

ride-thru

2

= Enabled – indefinite power loss

ride-thru, provided control
power is maintained

The setting of this parameter either enables or disables the ride-thru feature of the Drive. If
disabled, the unit will stop immediately whenever a power loss occurs. If enabled, the Drive will
continue to operate during a momentary power loss of up to 80%, but if the loss exceeds the
identified time period, the Drive will stop.

5.15 MOMENTARY POWER LOSS RIDE-THRU

n44 :

Multi-function Analog Output

Factory setting:

0

The monitor output provides a 0-10 Vdc signal
proportional to either output frequency or output current
between terminals AM & AC:

0

= 0-10 Vdc proportional

to output frequency

1

= 0-10 Vdc proportional

to output current

n45 :

Analog Monitor Gain

Factory Setting:

1.00

Range: 0.01 to 2.00

This constant is used to calibrate the meter connected to terminals AM & AC.

Drive

AM

Analog

output

AC

(0-10 Vdc)

MULTI-
FUNCTION
MONITOR
OUTPUT

+ –

FREQUENCY/ CURRENT

METER

(1mA FULL SCALE)

5.16 MULTI-FUNCTION ANALOG MONITOR OUTPUT (Term. AM and AC)

n45

= 0.30

100%

MAX. OUTPUT
FREQUENCY

Factory Setting

OR CURRENT.

(

n45

= 1.00)

0

3 V

10 V

ANALOG OUTPUT