6-6

Fault Display

Digital

RUN (Green)

Drive

Explanation

Causes and

Operator

ALARM (Red)

Status

Corrective Actions

EF

Check the external circuit

(External fault)

(sequence).

Drive receives an
external fault input from
control circuit terminal.
EF0: External fault

reference through
MODBUS
communications

EF2: External fault input

command from control
circuit terminal S2

EF3: External fault input

command from control
circuit terminal S3

EF4: External fault input

command from control

Protective

circuit terminal S4

Operation.

EF5: External fault input

Output is

command from control

shut OFF

circuit terminal S5

and motor

CPF-00

Cycle power after checking

coasts to

Drive cannot

the digital operator is

a stop.

communicate with the digital

securely mounted.

operator for 5 sec. or

If the fault remains,

more when power is

replace the digital operator

turned ON.

or drive.

CPF-01

Cycle power after checking

Transmission fault

the digital operator is

occurred for 5 sec or more

securely mounted.

when transmission starts

If the fault remains,

with the digital operator.

replace the digital operator
or drive.

CPF-04

• Record all parameter

EEPROM fault of drive

data and initialize the

control circuit is detected.

constants. (Refer to
paragraph 5.20 for
parameter initialization.)

• Cycle power.

If the fault remains,
replace the drive.

Table 6-2. Fault Displays and Corrective Actions - Continued