A.

n48 :

Number of Auto-Restart Attempts

Factory setting:

0

Range: 0 to 10

When a fault occurs during operation, the Drive can be programmed for an auto-restart operation to
automatically reset the fault. Auto-restart operation will use the number of reset attempts set in this
parameter, up to the maximum of 10. When set to " 0 ", no auto-restarts will be attempted.

• The following faults can be automatically reset:

oC:

Overcurrent

ou:

Overvoltage (OV)

GF:

Ground Fault

• The number of restart attempts available will be reset to the

n48

setting when:

1. 10 minutes has elapsed without a fault occurring.
2. The

RESET

key, or external Fault Reset push button, is pressed.

3. Power is removed from the Drive.

5.4 AUTO-RESTART