n40 :

Multi-function Output 1

Data

6

or

7

: Overtorque

(terminals MA, MB & MC)

Detection

The Form-C contact, or an open collector output, can be programmed to change states during an
overtorque detection condition.

EXAMPLE OF OVERTORQUE DETECTION

n59

setting:

2

— Overtorque enabled, only at set frequency, coast to stop

n40

setting:

6

— Output contact programmed for overtorque detection

n60

setting:

110

%

— Level at which overtorque is sensed

n61

setting:

1.0

s

— Time delay before overtorque event occurs

Detection level

(

n60

)

Detection

110%

time

OUTPUT

100%

(

n61)

CURRENT/

TORQUE

0

100%

Coast

MOTOR

stop

SPEED

0

RUN

SIGNAL

FAULT

SIGNAL

CONTACT

OUTPUT

(OVERTORQUE

DETECTION)

TERM. MA & MC)

Overtorque Detection Timing Diagram

5.19 OVERTORQUE DETECTION