beautypg.com

27 copy function, Copy function -38 – Yaskawa J7 Drive User Manual

Page 73

background image

5-38

The optional Remote Digital Operator can be used to store (upload) parameters from a drive, which
can then be copied (downloaded) to another drive. These parameters are stored in EEPROM in the
Digital Operator. The Copy Function is possible only for drives of the same type (i.e. from one J7 to
another, but not from a J7 to a V7 or vice versa), and voltage rating (230V drive or 460V drive). In
addition, the following parameters cannot be copied:

5.27 COPY FUNCTION

Parameter No.

Parameter Name

n09 to n15

V/f Settings

n32

Motor Rated Current

n46

Carrier Frequency

n64

Motor Rated Slip

n65

Motor No-load Current

n76

: Parameter Copy Function Selection

Ex :

Factory Setting: rdy

Setting

Description

rdy

Drive is ready to use Copy Function

rEd

Read (or upload) all parameters from the drive and store them in the Digital Operator

Cpy

Copy (or download) all parameters stored in the Digital Operator to the drive

vFy

Verify that parameters stored in the Digital Operator and the drive are the same

vA

Displays the voltage and kW rating of the drive whose parameters are stored in the
Digital Operator

Sno

Displays the software number of the drive whose parameters are stored in the
Digital Operator

n77

: Parameter Copy Access Selection

Factory Setting: 0

Range: 0 or 1

Setting

Description

0

Copying Disabled

1

Copying Allowed

The Copy Function can be enabled or disabled using parameter n77 – parameters cannot be
uploaded or downloaded when this parameter is disabled (n77 = 0), preventing the accidental
overwriting of parameters stored in either the Digital Operator or the Drive.

If n77 = 0 and an upload or download is attempted (n76 = rEd or Cpy), a “PrE” error message will
blink on the Digital Operator display – press DSPL or DATA/ENTER to clear the message.

For more detailed information on the use of the Copy Function, please visit our website at
www.drives.com.