beautypg.com

8 frequency reference bias/gain (analog), Frequency reference bias/gain (analog) -8 – Yaskawa J7 Drive User Manual

Page 43

background image

5-8

ADJUSTMENT PROCEDURE:

1.

With no input, adjust Bias (

n42

setting) until an output of

0.0 Hz is obtained.

2.

With full scale input, adjust Gain (

n41

setting) until an output

of 60.0 Hz (or other desired max. output frequency) is obtained.

NOTE: Follow the same adjustment procedure for other desired frequency setpoints.

n41 :

Analog Frequency Reference Gain

Factory setting:

100

%

Range: 0 to 255 %

Sets the auto-speed frequency command gain,
in increments of 1%.

n42 :

Analog Frequency Reference Bias

Factory setting:

0

%

Range: -99 to 99 %

10V

FREQ. REF.
INPUT (V)

FREQ.
REF.
(%)

BIAS

(+)

()

0V

100%

0%

–100%

BIAS

5.8 FREQUENCY REFERENCE BIAS/GAIN (ANALOG)

For inverse-acting frequency reference

1.

Begin with

n41

&

n42

settings as shown below.

2.

Fine tune as indicated above.

n41 n42

= 100 0

= 0 99

100%

FREQ

REF.

0%

0V

10V

INPUT VOLTAGE (TERM. FR)

FREQ. REF.
INPUT (V)

FREQ.
REF.
(%)

GAIN

110

100

90

10V

0V

100%

0%

(+)

()

GAIN

99%

–99%