5-33

n04 :

Stopping Method

Factory setting:

0

Range: 0 to 1

Selects the stopping method suitable for the application.

Setting

Description

0

Deceleration (ramp) to stop

1

Coast to stop

A.

Data

0

: Deceleration to Stop

Upon removal of the FWD (REV) Run
command, the motor decelerates at the
deceleration rate determined by the time
set in Decel Time 1 (

n17

), and DC

injection braking is applied immediately
before stop. If the decel time is too short
or the load inertia is too large, an
overvoltage (OV) fault may occur on a
stop command — the decel time must be
increased.

B.

Data

1

: Coast to Stop

Upon removal of the FWD (REV) Run command, the motor coasts to rest.

5.23 STOPPING METHOD

Output Frequency

Run Command

ON

OFF

Decel Time 1

(n17 )

Min. Output Frequency
(Frequency at DC Injection
Braking Start)

(n14 )

DC Injection Braking
Time at Stop

(n53 )

(Factory setting: 0.5 s)

Output Frequency

Run Command

ON

OFF

Drive output is shut OFF
when stop command is input