6-2

Alarm Display

Digital

RUN (Green)

Drive

Explanation

Causes and

Operator

ALARM (Red)

Status

Corrective Actions

OP

(Parameter setting

Check the setting values.

error when the parameter
setting is performed
through the MODBUS
communications)
OP1: Two or more values

are set for multi-
function input
selection.
(parameters

n36

to

n39

)

OP2: Relationship among

V / f parameters is not
correct.
(parameters

n09,

n11, n12, n14

)

Blinking

OP3: Setting value of

electronic thermal
standard current
exceeds 150% of
drive rated current.

Warning

(parameter

n32

)

only.

OP4: Upper / lower limit

Fault

of frequency

contacts

reference is reversed.

do not

(parameters

n32

,

change

n33

)

state.

OP5: (parameters

n49

and

n50

)

OP9: Carrier frequency

setting is incorrect.
(parameter

n46

)

OL 3 (Overtorque

Reduce the load, and

detection)

increase the accel / decel

Motor current exceeded

time.

the preset value in

Blinking

parameter

n60

.

SEr (Sequence error)

Check the external circuit

Drive receives

(sequence).

LOCAL / REMOTE select
command or

Blinking

communication / control
circuit terminal changing
signals from the multi-
function terminal while the
drive output is ON.

Table 6-1. Alarm Displays and Corrective Actions - Continued