1-6

DATA

FUNCTION

DESCRIPTION*

S1

Input 1

Factory setting is " Forward Run/Stop " (1).
(Forward run when closed, stop when open)

S2

Multi-Function-Input 2

Factory setting is " Reverse Run/Stop " (1).
(Reverse Run when closed, stop when open)

S3

Multi-Function-Input 3

Factory setting is " Fault Reset " (1).

S4

Multi-Function-Input 4

Factory setting is "External Fault
(NO contact)

" (1).

S5

Multi-Function-Input 5

Factory setting is " Multi-step Speed
Reference 1

" (1).

SC

Sequence common for terminals S1-S5.

Common terminal for sequence inputs.

FS

Frequency reference power supply

+12 VDC

FR

Frequency reference input

0 to +10V/100% (20K ohms) or 4-20 mA (250 Ω)

FC

Frequency reference input common

0 V

MA

Multi-function contact output – NO contact

Factory

Contact capacity:

MB

Multi-function contact output – NC contact Setting

250 Vac at 1A or below

MC

Multi-function contact output – Common

is "Drive

30 Vdc at 1A or below

Running

"

AM

Multi-function analog monitor (+) Factory setting is

" Output frequency "
0-10V = 0-100%

Monitor output: 0 to +10V; 2 mA maximum.

AC

Analog monitor common

0 V

Table 1-3. Terminal Functions and Signals of Control Circuit

NOTES:

1.

These inputs have factory settings based on 2-wire reset. For 3-wire reset definitions, see Figure 1-6.

Continued