Yaskawa J7 Drive User Manual
Page 18

1-6
DATA
FUNCTION
DESCRIPTION*
S1
Input 1
Factory setting is " Forward Run/Stop " (1).
(Forward run when closed, stop when open)
S2
Multi-Function-Input 2
Factory setting is " Reverse Run/Stop " (1).
(Reverse Run when closed, stop when open)
S3
Multi-Function-Input 3
Factory setting is " Fault Reset " (1).
S4
Multi-Function-Input 4
Factory setting is "External Fault
(NO contact)
" (1).
S5
Multi-Function-Input 5
Factory setting is " Multi-step Speed
Reference 1
" (1).
SC
Sequence common for terminals S1-S5.
Common terminal for sequence inputs.
FS
Frequency reference power supply
+12 VDC
FR
Frequency reference input
0 to +10V/100% (20K ohms) or 4-20 mA (250 Ω)
FC
Frequency reference input common
0 V
MA
Multi-function contact output – NO contact
Factory
Contact capacity:
MB
Multi-function contact output – NC contact Setting
250 Vac at 1A or below
MC
Multi-function contact output – Common
is "Drive
30 Vdc at 1A or below
Running
"
AM
Multi-function analog monitor (+) Factory setting is
" Output frequency "
0-10V = 0-100%
Monitor output: 0 to +10V; 2 mA maximum.
AC
Analog monitor common
0 V
Table 1-3. Terminal Functions and Signals of Control Circuit
NOTES:
1.
These inputs have factory settings based on 2-wire reset. For 3-wire reset definitions, see Figure 1-6.
Continued
1.4 ELECTRICAL INSTALLATION